ELE04-03557
| Electrical Rough-In | 2/8/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 2/8/2005 at 7:32:22 PM. Contact: ###-####. ceiling cover ok in kitchen area, roof ok, explained they need gfci's in kitchen area. 2/10/2005 9:01:59 AM
|
ELE04-03314
| Final | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PASS |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr about gfci in master br. cover off and recpt painted. ok to final 2/10/2005 10:18:28 AM
|
ELE05-00438
| Rough-In Permanent Service | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PASS |
|
|
darrell ###-#### ric ok p/s o/h n ok 2/10/2005 9:33:03 AM
|
ELE03-00866
| Final | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/9/2005 at 7:05:59 PM. Contact: ###-####. needs to put on cover for dryer recpt, and sw outlet showing open ground. Will call next week. Rest ok. 2/10/2005 9:49:52 AM
|
ELE05-00083
| Final | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn ok to final 2/10/2005 8:24:02 AM
|
ELE05-00082
| Final | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Bob Glenn ok to final 2/10/2005 8:14:25 AM
|
ELE05-00367
| Rough-In Permanent Service | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 7:46:55 AM. Contact: ###-####. 210.52(D) recpt to be 3' of sink in bathroom, 334.30 nm cable to be supported 4 1/2', 300.4(D) cable to be back 1 1/4" from edge, 300.4(A)(1) nailplates 2/10/2005 1:50:16 PM
|
ELE05-00457
| Temporary Service | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | FAIL |
|
|
zane ###-#### called contr, left corr notice 110.12(C) there shall be no broken parts. 2/10/2005 2:18:52 PM
|
ELE03-00815
| Final | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | PASS |
|
|
dan///please call at least a half hour prior to inspection so he can meet ya there; Phone #: ###-#### Internet Inspection Request from: Barbara Moore told contr he had to add strap to service cnd. ok to final 2/10/2005 4:26:29 PM
|
ELE05-00381
| Electrical Rough-In | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | PASS |
|
|
ufer ground re-insp. Contact Miles, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters two ufers provided. one inside and one outside of foundation. ok 2/10/2005 2:41:50 PM
|
ELE05-00241
| Conference | 2/9/2005 | 2/10/2005 | 2/9/2005 2:45:36 PM | P | CANC |
|
|
consultaion, please contact Matt Murray. Thank You; Phone #: ###-#### Internet Inspection Request from: Wendy Waters Inspection cancelled from web by: Wendy Waters
|