Inspections for the day of: Thursday, February 10, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03557 Electrical Rough-In2/8/20052/10/20052/10/2005 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 2/8/2005 at 7:32:22 PM. Contact: ###-####. ceiling cover ok in kitchen area, roof ok, explained they need gfci's in kitchen area. 2/10/2005 9:01:59 AM
ELE04-03314 Final2/9/20052/10/20052/10/2005 12:00:00 AMAPASS
jack; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr about gfci in master br. cover off and recpt painted. ok to final 2/10/2005 10:18:28 AM
ELE05-00438 Rough-In Permanent Service2/9/20052/10/20052/10/2005 12:00:00 AMAPASS
darrell ###-#### ric ok p/s o/h n ok 2/10/2005 9:33:03 AM
ELE03-00866 Final2/9/20052/10/20052/10/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/9/2005 at 7:05:59 PM. Contact: ###-####. needs to put on cover for dryer recpt, and sw outlet showing open ground. Will call next week. Rest ok. 2/10/2005 9:49:52 AM
ELE05-00083 Final2/10/20052/10/20052/10/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn ok to final 2/10/2005 8:24:02 AM
ELE05-00082 Final2/10/20052/10/20052/10/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn ok to final 2/10/2005 8:14:25 AM
ELE05-00367 Rough-In Permanent Service2/10/20052/10/20052/10/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/10/2005 at 7:46:55 AM. Contact: ###-####. 210.52(D) recpt to be 3' of sink in bathroom, 334.30 nm cable to be supported 4 1/2', 300.4(D) cable to be back 1 1/4" from edge, 300.4(A)(1) nailplates 2/10/2005 1:50:16 PM
ELE05-00457 Temporary Service2/10/20052/10/20052/10/2005 12:00:00 AMPFAIL
zane ###-#### called contr, left corr notice 110.12(C) there shall be no broken parts. 2/10/2005 2:18:52 PM
ELE03-00815 Final2/10/20052/10/20052/10/2005 12:00:00 AMPPASS
dan///please call at least a half hour prior to inspection so he can meet ya there; Phone #: ###-#### Internet Inspection Request from: Barbara Moore told contr he had to add strap to service cnd. ok to final 2/10/2005 4:26:29 PM
ELE05-00381 Electrical Rough-In2/10/20052/10/20052/10/2005 12:00:00 AMPPASS
ufer ground re-insp. Contact Miles, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters two ufers provided. one inside and one outside of foundation. ok 2/10/2005 2:41:50 PM
ELE05-00241 Conference2/9/20052/10/20052/9/2005 2:45:36 PMPCANC
consultaion, please contact Matt Murray. Thank You; Phone #: ###-#### Internet Inspection Request from: Wendy Waters Inspection cancelled from web by: Wendy Waters