FIR04-00258
| INSP-Sprinkler Rough-in/Hydro | 2/10/2005 | 2/10/2005 | 2/10/2005 1:20:40 PM | P | CANC |
|
|
contact: Steve - cover inspection late PM if possible; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR04-00704
| FIR-Aging Inspection | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | | NR |
|
|
I call Mike Martin ###-####/###-#### requesting status of job. No answer so I left message. 2/11/2005 12:29:28 PM
|
FIR04-00603
| INSP-Final Inspection | 2/3/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR04-00149
| INSP-Final Inspection | 2/4/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | FAIL |
|
|
Provide additional a/v in truck delivery on circuit av-8. Repair a/v9-3 in storage supply. Set high/low pressure switch and test. Liebert #4 does not shut down. Test supervision between new panel/nac's and the existing system. Provide map at new panel and existing panel. Remove old equipment. Resend alarm, trouble and supervisory signals to central station. Verify if existing tamper can remain on old system and if heats need to be shown on new plans. 2/10/2005 8:18:01 AM
|
MIS05-00003
| FIR-Final | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given until all outlet covers are on and the occupant load signs have been posted. I told contractor to contact ron hill on the floor plan change 2/10/2005 11:43:34 AM
|
BLD04-02820
| FIRE-Final Inspection | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/10/2005 11:19:31 AM
|
BLD04-02775
| FIRE-Final Inspection | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | A | NR |
|
|
Inspection was for placement of emergency lights. Two are needed in the open classroom with one shining down the short corridor and one in the small west side classroom. The exit sign at the main exit needs repaired. Remove the round door knobs and provide approved hardware on the two interior doors and provide approved hardware on the second store front door or get approval to remove hardware and cover door. 2/10/2005 9:09:39 AM
|
FIR05-00054
| INSP-Sprinkler Rough-in | 2/9/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | PASS |
|
|
Sprinkler piping is ok to cover 2/10/2005 10:47:56 AM
|
BLD04-01847
| FIRE-Final Inspection | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | CANC |
|
|
To be rescheduled for next week per Jim 2/10/2005 11:44:32 AM
|
BLD04-02088
| FIRE-Final Inspection | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 2/10/2005 3:48:10 PM
|
FIR04-00670
| INSP-Final Inspection | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinklers finaled
|
FIR04-00744
| INSP-Sprinkler Rough-in/Hydro | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | FAIL |
|
|
Looked at tie in but could not inspect the rest of the work due to GE calibrating the MRI machine. 2/10/2005 1:33:50 PM
|
FIR04-00666
| INSP-Sprinkler Rough-in/Hydro | 2/10/2005 | 2/10/2005 | 2/10/2005 12:00:00 AM | P | PART |
|
|
west wing ok to cover 2/11/2005 7:56:21 AM
|