BLD10-00192
| FIRE-Final Inspection | 2/10/2010 | 2/10/2010 | 2/10/2010 3:44:33 PM | P | FAIL |
|
|
Remove the round knob door hardware and provide singel action lever hardware, provide sticker, and mount the K class fire extinguisher off of the floor.
|
BLD09-01717
| FIRE-Final Inspection | 2/9/2010 | 2/10/2010 | 2/10/2010 3:32:13 PM | P | CANC |
|
|
Cancelled per Bill Phone #: ###-####
|
FIR09-00708
| INSP-Sprinkler Rough-in | 2/10/2010 | 2/10/2010 | 2/10/2010 2:30:42 PM | P | PASS |
|
|
The 24 hour air test on system 4 passed.
|
FIR10-00031
| INSP-Sprinkler Rough-in | 2/9/2010 | 2/10/2010 | 2/10/2010 1:24:56 PM | A | PART |
|
|
The sprinkler piping can be covered. I noted that two of the new extended coverage pendants at the Lobby are less than 8' apart. The solution will be verified at the final inspection. The riser also has a current inspection tag.
|
BLD09-00323
| FIRE-Final Inspection | 2/9/2010 | 2/10/2010 | 2/10/2010 11:24:11 AM | A | CANC |
|
|
Wrong inspection type set up.
|
FIR09-00731
| INSP-Supply line flush | 2/9/2010 | 2/10/2010 | 2/10/2010 10:41:33 AM | A | PASS |
|
|
The underground supply line flush passed.
|
BLD10-00173
| FIRE-Final Inspection | 2/9/2010 | 2/10/2010 | 2/10/2010 9:38:53 AM | A | FAIL |
|
|
Provide singel action hardware on the rear exit door such as lever action or panic. Thumbturn locks are not allowed. Also the existing fire sprinkler system requires modifications to meet code requirements. This work requires a separate permit by a licensed fire sprinkler contractor.
|
BLD10-00173
| FIRE-Hydro test above ground | 2/9/2010 | 2/10/2010 | 2/10/2010 9:37:04 AM | A | CANC |
|
|
Wrong inspection type set up.
|