Inspections for the day of: Thursday, February 10, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00560 INSP-Final Inspection2/9/20112/10/20112/10/2011 4:01:39 PMPPART
Fire alarm work passed functional testing. Final pending accurate account information at offsite monitoring regarding zone descriptors and signals recieved.
BLD10-02486 FIRE-Final Inspection2/9/20112/10/20112/10/2011 3:58:24 PMPPASS
Fire life safety passed. Note: door hardware at the reception desk to be reversed for compliance with egress req.- prior to structrual inspection.
BLD10-02371 FIRE-Final Inspection2/9/20112/10/20112/10/2011 3:54:36 PMAPASS
Fire life safety final okayed. Note: fire alarm permit under review for the radio transmitter addition to the exisitng FACP.
FIR11-00016 INSP-Final Inspection2/9/20112/10/20112/10/2011 3:52:47 PMAPASS
Recieved as-built plans from contractor regarding deleted head at the covered patio per NFPA 13 2007 8.15.7.3(1) exception. C/N items finished, permit finaled.
FIR10-00659 INSP-Sprinkler Rough-in2/9/20112/10/20112/10/2011 3:49:05 PMAPART
Overhead rough-in passed inspection, noted sw heads at the garages are not yet installed, riser or supply manifolds are not ready at this time. Contractor to call for inspection of batt insulation at the first floor piping prior to cover- (tented areas okayed).
BLD10-02572 FIRE-Final Inspection2/9/20112/10/20112/10/2011 3:44:05 PMAPASS
Fire life safety passed.
FIR10-00649 INSP-Final Inspection2/9/20112/10/20112/10/2011 3:43:24 PMAPASS
Reinspection passed, permit finaled.
FIR11-00016 INSP-Final Inspection2/9/20112/10/20112/9/2011 4:39:03 PMACANC
jason Phone #: ###-#### Inspection cancelled from web by: Stan Beus