Inspections for the day of: Tuesday, February 10, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-02980 FIRE-Final Inspection2/10/20152/10/20152/12/2015 2:49:42 PMPFAIL
Emergency light at the main lobby/counter needs replaced still
BLD15-00081 FIRE-Final Inspection2/10/20152/10/20152/10/2015 3:20:59 PMPPART
A temporary for life safety is being given unitl the overhead door is installed and the project related fire sprinkler work, for this door, is complete.
BLD14-03582 FIRE-Final Inspection2/10/20152/10/20152/10/2015 2:38:26 PMPFAIL
Repair non-functional exit signs and emergency ligths, provide exit sign/emergency light is foyer, provide sticker at foyer door, provide annual inspeciton for the fire extinguishers and verification the annual inspection has been performed of the fire sprinkler system, change locking door hardware into the reception area, provide corrected occupant load sign
FIR15-00008 INSP-Sprinkler Rough-in2/10/20152/10/20152/10/2015 1:21:54 PMPPASS
Rough-in passed. Piping can be covered.
FIR14-00848 INSP-Sprinkler Rough-in/Hydro2/9/20152/10/20152/10/2015 1:21:18 PMPPART
Overhead hydro tests passed, rough-in passed except the pendant heads in the restrooms are too close together based on extended coverage requirements. Tenting was not complete. Pipe not to be covered.
FIR14-00818 INSP-Sprinkler Rough-in/Hydro2/9/20152/10/20152/10/2015 1:19:48 PMAPASS
Overhead hydro and rough-in passed.
FIR14-00871 INSP-Sprinkler Rough-in2/9/20152/10/20152/10/2015 1:05:37 PMPPASS
See the city approved plans for three additional rooms where piping is ok to cover.
BLD14-03461 FIRE-Final Inspection2/9/20152/10/20152/10/2015 9:45:24 AMAPASS
Remove deadbolt hardware or get plan review approval on the north exit door from office, remove deadbolt on exit door from therapy area prior to building inspection.
BLD14-02274 FIRE-Final Inspection2/9/20152/10/20152/9/2015 3:22:06 PMAPASS
Life safety passed
FIR14-00848 INSP-Sprinkler Rough-in2/9/20152/10/20152/9/2015 1:44:41 PMPCANC
RTC inspection. Mike M is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus