FIR16-00045
| INSP-Sprinkler Rough-in | 2/10/2016 | 2/10/2016 | 2/10/2016 3:53:03 PM | P | PASS |
|
|
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.
|
FIR15-00398
| INSP-Sprinkler Rough-in | 2/10/2016 | 2/10/2016 | 2/10/2016 3:44:35 PM | P | PASS |
|
|
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.
|
FIR15-00396
| INSP-Sprinkler Rough-in | 2/10/2016 | 2/10/2016 | 2/10/2016 3:43:29 PM | P | PASS |
|
|
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.
|
FIR15-00912
| INSP-Sprinkler Rough-in/Hydro | 2/10/2016 | 2/10/2016 | 2/10/2016 1:45:44 PM | P | PASS |
|
|
Underground hydrostatic (200psi for 2 hours) test passed/complete.
|
FIR15-00814
| INSP-Final Inspection | 2/10/2016 | 2/10/2016 | 2/10/2016 1:20:21 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR15-00889
| INSP-Final Inspection | 2/9/2016 | 2/10/2016 | 2/10/2016 10:27:10 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR13-00312
| INSP-Final Inspection | 2/10/2016 | 2/10/2016 | 2/10/2016 10:23:13 AM | A | PART |
|
|
Devices associated with fire sprinkler systems tested, tampers, flow switches, high/low air switches and pre-action pressure switches, devices operated correctly, water flow pressure switches on pre-action systems reported to fire panel as a supervisory, pre-action flow switches will be reprogrammed to come in as water flow alarm with exterior bell activation. Riser rooms inspected/tested were located on the east side of building and southeast side of building.
|
FIR15-00815
| INSP-Final Inspection | 2/10/2016 | 2/10/2016 | 2/10/2016 10:14:32 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR15-00390
| INSP-Final Inspection | 2/10/2016 | 2/10/2016 | 2/10/2016 10:13:44 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00076
| INSP-Sprinkler Rough-in | 2/9/2016 | 2/10/2016 | 2/10/2016 8:52:15 AM | A | PASS |
|
|
Rough to cover inspection for the hardlids passed/complete, notated with red ink on the city approved drawings were cover is approved.
|
BLD16-00353
| FIRE-Final Inspection | 2/9/2016 | 2/10/2016 | 2/10/2016 8:33:01 AM | A | PASS |
|
|
No modifications to fire sprinklers, no fire alarms, fire extinguishers have current inspection tag. Exit sign on west exit missing cover, POC will replace cover. Life fire safety inspection passed/complete
|