Inspections for the day of: Wednesday, February 10, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00045 INSP-Sprinkler Rough-in2/10/20162/10/20162/10/2016 3:53:03 PMPPASS
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.
FIR15-00398 INSP-Sprinkler Rough-in2/10/20162/10/20162/10/2016 3:44:35 PMPPASS
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.
FIR15-00396 INSP-Sprinkler Rough-in2/10/20162/10/20162/10/2016 3:43:29 PMPPASS
Rough to cover inspection passed/complete for the underground fire sprinkler supply line, underground approved for cover.
FIR15-00912 INSP-Sprinkler Rough-in/Hydro2/10/20162/10/20162/10/2016 1:45:44 PMPPASS
Underground hydrostatic (200psi for 2 hours) test passed/complete.
FIR15-00814 INSP-Final Inspection2/10/20162/10/20162/10/2016 1:20:21 PMPPASS
Final fire sprinkler inspection passed/complete.
FIR15-00889 INSP-Final Inspection2/9/20162/10/20162/10/2016 10:27:10 AMPPASS
Final fire sprinkler inspection passed/complete
FIR13-00312 INSP-Final Inspection2/10/20162/10/20162/10/2016 10:23:13 AMAPART
Devices associated with fire sprinkler systems tested, tampers, flow switches, high/low air switches and pre-action pressure switches, devices operated correctly, water flow pressure switches on pre-action systems reported to fire panel as a supervisory, pre-action flow switches will be reprogrammed to come in as water flow alarm with exterior bell activation. Riser rooms inspected/tested were located on the east side of building and southeast side of building.
FIR15-00815 INSP-Final Inspection2/10/20162/10/20162/10/2016 10:14:32 AMAPASS
Final fire alarm inspection passed/complete
FIR15-00390 INSP-Final Inspection2/10/20162/10/20162/10/2016 10:13:44 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00076 INSP-Sprinkler Rough-in2/9/20162/10/20162/10/2016 8:52:15 AMAPASS
Rough to cover inspection for the hardlids passed/complete, notated with red ink on the city approved drawings were cover is approved.
BLD16-00353 FIRE-Final Inspection2/9/20162/10/20162/10/2016 8:33:01 AMAPASS
No modifications to fire sprinklers, no fire alarms, fire extinguishers have current inspection tag. Exit sign on west exit missing cover, POC will replace cover. Life fire safety inspection passed/complete