Inspections for the day of: Friday, February 10, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04017 Electrical Rough-In2/9/20172/10/20172/10/2017 1:51:42 PMAPASS
North ; South Stairwell....George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Area noted rough in ok cover
ELE17-00324 Electrical Rough-In2/9/20172/10/20172/10/2017 1:09:44 PMPPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Phase 2 will be 2 conference rooms and 1 office. Today phase 1, 3 offices, break and work area wall rough in ok cover
ELE16-03412 Final2/9/20172/10/20172/10/2017 1:05:51 PMPPASS
9th floor correction inspection Phone #: ###-#### Inspection requested via web by steve ragan Final ok
ELE15-01348 Conference2/10/20172/10/20172/10/2017 11:24:53 AMPDONE
Spoke with Joe, General Foreman with Hoffman to address incomplete raceway covers and firewall penetrations on elevator wireways. Annex 5th floor elevator control room and elevator lobby. All will need to by completed before final inspection.
ELE17-00244 Electrical Rough-In2/9/20172/10/20172/10/2017 10:05:48 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
210.52(B)- All receptacle outlets located in kitchen and dining areas shall be fed by a 20 amp small appliance circuit. 2 on north wall of kitchen dining area.