FIR16-00319
| INSP-Sprinkler Rough-in | 2/10/2017 | 2/10/2017 | 2/10/2017 1:52:16 PM | P | CANC |
|
|
Request is rescheduled for 13FEB2017
|
FIR16-00556
| INSP-Sprinkler Rough-in/Hydro | 2/10/2017 | 2/10/2017 | 2/10/2017 1:50:59 PM | P | PART |
|
|
Partial rough to cover inspection complete for levels 1, mezzanine, and level 2, notated the city approved drawings with yellow highlighter red ink area's approved for cover. Rough in inspection is complete for level 3 in highlighted area on city approved drawings. Level 3 piping cannot be covered until tenting inspection is complete and passed.
|
BLD16-04442
| FIRE-Final Inspection | 2/9/2017 | 2/10/2017 | 2/10/2017 10:12:54 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher will be mounted in discussed location. Final life fire safety inspection passed/complete.
|
BLD15-02643
| FIRE-Final Inspection | 2/8/2017 | 2/10/2017 | 2/10/2017 9:36:22 AM | A | PASS |
|
|
No fire sprinklers, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00754
| INSP-Final Inspection | 2/7/2017 | 2/10/2017 | 2/10/2017 12:00:00 AM | P | CANC |
|
|
Cancel per Paul with AAA Fire Safety and Alarm Inc. will call another time to schedule paul Phone #: ###-####
|