Inspections for the day of: Wednesday, February 11, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03450 ELE-Aging Inspection2/11/20042/11/20042/11/2004 12:00:00 AM PASS
ok 2/11/2004 11:31:03 AM
ELE03-03449 ELE-Aging Inspection2/11/20042/11/20042/11/2004 12:00:00 AM CANC
sign removed store is out of business 2/11/2004 9:54:21 AM
ELE03-03787 ELE-Aging Inspection2/11/20042/11/20042/11/2004 12:00:00 AM DONE
finaled 2/11/2004 9:05:30 AM
ELE04-00385 Final2/10/20042/11/20042/11/2004 12:00:00 AMAPASS
darrel; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 2/11/2004 1:18:29 PM
ELE04-00354 Temporary Service2/10/20042/11/20042/11/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/10/2004 at 2:00:55 PM. Contact: ###-####. t/s o/h new ok 2/11/2004 8:34:16 AM
ELE04-00311 Permanent Service2/10/20042/11/20042/11/2004 12:00:00 AMAPASS
roll up door will be open. Ok to go in by owner.; Phone #: ###-#### Internet Inspection Request from: Andy Rose called needs lioght for both exit doors and 30" wide in front of panel

p/s o/h new ok 2/11/2004 9:03:10 AM
ELE03-04099 Final2/11/20042/11/20042/11/2004 12:00:00 AMPFAIL
dan ; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 410.8 MB closet 2/11/2004 3:43:36 PM
ELE03-04120 Final2/11/20042/11/20042/11/2004 12:00:00 AMPFAIL
dan ; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 410.8 closet, 250.148 grd wiremold boxes and 300.14 needs 6" at wiremold boxes 2/11/2004 3:14:04 PM
ELE03-03482 Final2/11/20042/11/20042/11/2004 12:00:00 AMPFAIL
ED; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted called 110.3(B) manufactures breakers only, 110.26 clearence for p/s, remove phone equip. from below and required clearence for sub panel, 250 p/s and sub panel, ged and bond to p/s, address what was p/s as sub panel addess range and dryer feeds, 220 calculate service for proper size 2/11/2004 2:37:30 PM
ELE03-00815 Rough-In Permanent Service2/11/20042/11/20042/11/2004 12:00:00 AMPPASS
DAN (please call for access); Phone #: ###-#### Internet Inspection Request from: Annette Moore r/i ok
p/s u/g new ok 2/11/2004 12:46:13 PM