FIR03-00678
| FIR-Aging Inspection | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | | NR |
|
|
I spoke to Mike with General Fire and he stated that the project is complete and that he would call in an inspection 2/11/2004 12:52:08 PM
|
FIR03-00719
| INSP-Final Inspection | 2/10/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 2/11/2004 11:13:58 AM
|
FIR02-00388
| INSP-Final Inspection | 2/10/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | A | FAIL |
|
|
hanger attachments for the trapeze hanger must meet figure 18 of the installation instructions, provide the requirements of review note "n" for hose valve. Provide column protection per plans. Complete work in room 115 and provide calculations per review note "m". Provide 6" longitudinal flu spaces between double row racks. Provide max storage hieght signs 2/11/2004 10:07:09 AM
|
FIR03-00463
| INSP-Final Inspection | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | A | PASS |
|
|
Hood suppression system operated correctly
|
BLD03-01116
| FIRE-Final Inspection | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety, fire sprinkler and fire alarm finaled
|
FIR04-00024
| INSP-Sprinkler Rough-in | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | P | FAIL |
|
|
need approved insulation detail on site prior to inspection 2/11/2004 2:45:22 PM
|
BLD03-01945
| FIRE-Final Inspection | 2/10/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 2/11/2004 1:50:45 PM
|
FIR04-00049
| INSP-Sprinkler Rough-in | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | P | PASS |
|
|
Mick -- plans are in the window. thanks.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD03-02533
| FIRE-Final Inspection | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | P | FAIL |
|
|
Post occupant load signs per sheet A-1.2. Provide approved door hardware, see sheet A-1.2. Verify exit signs and emergency lights operate on backup power. Provide "door to remain unlocked during business hours" sticker at the main entry/exit, see sheet A-1.2.
Mount fire extinguishers at 48", see fire review note #3. Manual flush bolts on the main entry/exit are not allowed. Automatic flush bolts are. See fire review note #3. Final fire sprinkler permit. Remove address on the 5 mile street side if not to be used. 2/11/2004 2:31:26 PM
|
FIR03-00780
| INSP-Sprinkler Rough-in/Hydro | 2/11/2004 | 2/11/2004 | 2/11/2004 12:00:00 AM | P | FAIL |
|
|
provide hangers on the 1 1/4" supplies and the sprinkler pendant in the mechanical room is still overspaced 2/11/2004 3:40:51 PM
|