Inspections for the day of: Wednesday, February 11, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00678 FIR-Aging Inspection2/11/20042/11/20042/11/2004 12:00:00 AM NR
I spoke to Mike with General Fire and he stated that the project is complete and that he would call in an inspection 2/11/2004 12:52:08 PM
FIR03-00719 INSP-Final Inspection2/10/20042/11/20042/11/2004 12:00:00 AMAPASS
fire alarm finaled 2/11/2004 11:13:58 AM
FIR02-00388 INSP-Final Inspection2/10/20042/11/20042/11/2004 12:00:00 AMAFAIL
hanger attachments for the trapeze hanger must meet figure 18 of the installation instructions, provide the requirements of review note "n" for hose valve. Provide column protection per plans. Complete work in room 115 and provide calculations per review note "m". Provide 6" longitudinal flu spaces between double row racks. Provide max storage hieght signs 2/11/2004 10:07:09 AM
FIR03-00463 INSP-Final Inspection2/11/20042/11/20042/11/2004 12:00:00 AMAPASS
Hood suppression system operated correctly
BLD03-01116 FIRE-Final Inspection2/11/20042/11/20042/11/2004 12:00:00 AMAPASS
Fire life safety, fire sprinkler and fire alarm finaled
FIR04-00024 INSP-Sprinkler Rough-in2/11/20042/11/20042/11/2004 12:00:00 AMPFAIL
need approved insulation detail on site prior to inspection 2/11/2004 2:45:22 PM
BLD03-01945 FIRE-Final Inspection2/10/20042/11/20042/11/2004 12:00:00 AMPPASS
fire life safety finaled 2/11/2004 1:50:45 PM
FIR04-00049 INSP-Sprinkler Rough-in2/11/20042/11/20042/11/2004 12:00:00 AMPPASS
Mick -- plans are in the window. thanks.; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
BLD03-02533 FIRE-Final Inspection2/11/20042/11/20042/11/2004 12:00:00 AMPFAIL
Post occupant load signs per sheet A-1.2. Provide approved door hardware, see sheet A-1.2. Verify exit signs and emergency lights operate on backup power. Provide "door to remain unlocked during business hours" sticker at the main entry/exit, see sheet A-1.2.
Mount fire extinguishers at 48", see fire review note #3. Manual flush bolts on the main entry/exit are not allowed. Automatic flush bolts are. See fire review note #3. Final fire sprinkler permit. Remove address on the 5 mile street side if not to be used. 2/11/2004 2:31:26 PM
FIR03-00780 INSP-Sprinkler Rough-in/Hydro2/11/20042/11/20042/11/2004 12:00:00 AMPFAIL
provide hangers on the 1 1/4" supplies and the sprinkler pendant in the mechanical room is still overspaced 2/11/2004 3:40:51 PM