Inspections for the day of: Friday, February 11, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00367 Rough-In Permanent Service2/10/20052/11/20052/11/2005 12:00:00 AMAPASS
called contractor to staple one wire, and to put on a couple of nailplates. ric ok p/s u/g n ok 2/11/2005 10:05:28 AM
ELE05-00372 Electrical Rough-In2/10/20052/11/20052/11/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/10/2005 at 4:56:31 PM. Contact: ###-####. 110.26(A)(1) depth of work space shall be 3', 358.26 there shall be max 360 degree bends, 348.30 fmc shall be supported witin 12" of box, 210.63 gfci shall be provided on roof for refrigeration units, 110.3(B) equipment shall be listed 2/11/2005 11:51:54 AM
ELE05-00241 Conference2/9/20052/11/20052/11/2005 12:00:00 AMADONE
Please call at least a half hour prior to inspection///consultation, please contact Matt Murray, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters talked about code requirement to install raceways and to bring exst raceways up to code. Specifically flex to floor boxes. 2/11/2005 8:39:29 AM
ELE05-00458 Final2/10/20052/11/20052/11/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final 2/11/2005 8:26:45 AM
ELE05-00284 Electrical Rough-In2/10/20052/11/20052/11/2005 12:00:00 AMPPASS
Underground Insp. Please contact Steve, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to cover conduit from south towards fence for power and to west towards fence for power and communications. 2/11/2005 4:45:57 PM
ELE04-03339 Final2/11/20052/11/20052/11/2005 12:00:00 AMPFAIL
allen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 110.12(C) there shall be no damaged parts(service riser), 352.30(A) rnc shall be supported within 3" of box, 406.4 recepts shall be securely fastened called contr, left corr notice 2/11/2005 12:21:11 PM
ELE04-02595 Electrical Rough-In2/11/20052/11/20052/11/2005 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 2/11/2005 at 8:39:31 AM. Contact: ###-####. 2nd floor so of elev bath clg ric 2/11/2005 2:56:04 PM
ELE05-00206 Rough-In Permanent Service2/11/20052/11/20052/11/2005 12:00:00 AMPPASS
Plans are on site per builder, Wayne Swanson ###-####; Phone #: ###-#### Internet Inspection Request from: William Zerfas called contr, left survey for250.64(D) grounding electrode conductor shall not be spliced in panel 2/11/2005 2:05:13 PM
ELE05-00465 Rough-In Permanent Service2/11/20052/11/20052/11/2005 12:00:00 AMPFAIL
dale ###-####210.52(A)(1) recepts shall be spaced so no point is over 6' from recpt. 2/11/2005 1:03:36 PM