Inspections for the day of: Friday, February 11, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00258 INSP-Sprinkler Rough-in/Hydro2/10/20052/11/20052/11/2005 7:34:22 AMACANC
contact: Steve; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
FIR04-00701 FIR-Aging Inspection2/11/20052/11/20052/11/2005 12:00:00 AM NR
Per Jim Shelton work is in progress. Jim ###-#### 2/11/2005 9:44:37 AM
MIS05-00002 FIR-Final2/10/20052/11/20052/11/2005 12:00:00 AMAPART
###-####- wilson A temporary occupancy was given until exit signs/emergency lights are provided at main exit, arch in basement and the top of the stairs in the basement beyond the arch. Remove bar, thumbturn and round knob at top of stairs and provide with approved hardware. 2/11/2005 10:41:47 AM
FIR04-00744 INSP-Sprinkler Rough-in/Hydro2/10/20052/11/20052/11/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/10/2005 at 3:33:45 PM. Contact: ###-####.
BLD04-02775 FIRE-Final Inspection2/10/20052/11/20052/11/2005 12:00:00 AMAFAIL
Need door hardware removed from the west front door and the exit sign blanked off. Repair exit sign at the other front door. 2/11/2005 9:31:01 AM
FIR04-00574 INSP-Final Inspection2/9/20052/11/20052/11/2005 12:00:00 AMAPASS
Fire alarm finaled 2/11/2005 8:24:20 AM
BLD03-03027 FIRE-Final Inspection2/10/20052/11/20052/11/2005 12:00:00 AMAPASS
Fire life safety finaled 2/11/2005 8:43:36 AM
BLD04-02204 FIRE-Final Inspection2/10/20052/11/20052/11/2005 12:00:00 AMAPASS
fire life safety finaled 2/11/2005 10:12:43 AM
FIR04-00712 INSP-Final Inspection2/9/20052/11/20052/11/2005 12:00:00 AMPPASS
Finaled by Mary 2/11/2005 2:55:15 PM
FIR04-00674 INSP-Sprinkler Rough-in/Hydro2/11/20052/11/20052/11/2005 12:00:00 AMPFAIL
Hydro test failed twice today. I told fitter to hydro test system prior to me being called for test. Next one will be charged a re-inspection fee if it fails. 2/11/2005 3:00:32 PM
FIR05-00037 INSP-Sprinkler Rough-in2/11/20052/11/20052/11/2005 12:00:00 AMPFAIL
Floor plan does not match fire sprinkler plans. Piping sizing on plan does not match field. Quick responce and standard responce heads are mixed and different temperatures from listing on plans. Sidewall head too far from ceiling. One pendant not installed yet. Two uprights blocked by new soffits. Inspection stopped. Plans need to be resubmitted. 2/11/2005 4:17:02 PM
FIR05-00001 INSP-Sprinkler Rough-in/Hydro2/11/20052/11/20052/11/2005 12:00:00 AMPFAIL
New piping does not match plans. Resubmit 2/11/2005 4:17:35 PM