FIR04-00258
| INSP-Sprinkler Rough-in/Hydro | 2/10/2005 | 2/11/2005 | 2/11/2005 7:34:22 AM | A | CANC |
|
|
contact: Steve; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR04-00701
| FIR-Aging Inspection | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | | NR |
|
|
Per Jim Shelton work is in progress. Jim ###-#### 2/11/2005 9:44:37 AM
|
MIS05-00002
| FIR-Final | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PART |
|
|
###-####- wilson A temporary occupancy was given until exit signs/emergency lights are provided at main exit, arch in basement and the top of the stairs in the basement beyond the arch. Remove bar, thumbturn and round knob at top of stairs and provide with approved hardware. 2/11/2005 10:41:47 AM
|
FIR04-00744
| INSP-Sprinkler Rough-in/Hydro | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 3:33:45 PM. Contact: ###-####.
|
BLD04-02775
| FIRE-Final Inspection | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | FAIL |
|
|
Need door hardware removed from the west front door and the exit sign blanked off. Repair exit sign at the other front door. 2/11/2005 9:31:01 AM
|
FIR04-00574
| INSP-Final Inspection | 2/9/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled 2/11/2005 8:24:20 AM
|
BLD03-03027
| FIRE-Final Inspection | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/11/2005 8:43:36 AM
|
BLD04-02204
| FIRE-Final Inspection | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 2/11/2005 10:12:43 AM
|
FIR04-00712
| INSP-Final Inspection | 2/9/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | PASS |
|
|
Finaled by Mary 2/11/2005 2:55:15 PM
|
FIR04-00674
| INSP-Sprinkler Rough-in/Hydro | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | FAIL |
|
|
Hydro test failed twice today. I told fitter to hydro test system prior to me being called for test. Next one will be charged a re-inspection fee if it fails. 2/11/2005 3:00:32 PM
|
FIR05-00037
| INSP-Sprinkler Rough-in | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | FAIL |
|
|
Floor plan does not match fire sprinkler plans. Piping sizing on plan does not match field. Quick responce and standard responce heads are mixed and different temperatures from listing on plans. Sidewall head too far from ceiling. One pendant not installed yet. Two uprights blocked by new soffits. Inspection stopped. Plans need to be resubmitted. 2/11/2005 4:17:02 PM
|
FIR05-00001
| INSP-Sprinkler Rough-in/Hydro | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | FAIL |
|
|
New piping does not match plans. Resubmit 2/11/2005 4:17:35 PM
|