ELE05-00352
| Final | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | NR |
|
|
jimmy ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
work not complete 2/11/2005 12:42:02 PM
|
ELE05-00420
| Electrical Rough-In | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PASS |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ri ok survey recep spacing 2/11/2005 9:21:58 AM
|
ELE05-00436
| Rough-In Permanent Service | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | PASS |
|
|
Darrel; Phone #: ###-#### Internet Inspection Request from: Jan Rice
ri ok
p/s o/h n ok 2/11/2005 9:54:33 AM
|
ELE04-03557
| Final | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 4:43:29 PM. Contact: ###-####.
210.8B3 gfci outlets required for kitchens
did not look at rooftop, bathrooms and lobby area ok 2/11/2005 10:36:54 AM
|
ELE05-00452
| Final | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 10:24:29 PM. Contact: ###-#### call before you go
no access with the dogs in the yard 2/11/2005 9:34:26 AM
|
ELE05-00463
| Rough-In Permanent Service | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | CANC |
|
|
###-#### - clyde
|
ELE04-02543
| Final | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | FAIL |
|
|
Brett-call first; Phone #: ###-#### Internet Inspection Request from: Jan Rice
corrections still not made, elevator equipment signage,recedpticle, light, protection of low-voltage wiring with bushings, water grounding- where does it tie to the main system? 2/11/2005 3:00:24 PM
|
ELE05-00440
| Electrical Rough-In | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | PART |
|
|
Darrel; Phone #: ###-#### Internet Inspection Request from: Jan Rice
walls only in new tennant space 1st floor. ok to cover. 2/11/2005 3:26:54 PM
|
ELE04-03596
| Permanent Service | 2/11/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | FAIL |
|
|
###-#### - kelly
ufer not landed in gear, no visible means of bonding between the two gear sections (no manufacturer instructions on site that deals with bonding), no plastic bushings on the conduits.
250.92, 300.4, 2/11/2005 1:46:55 PM
|
ELE05-00239
| Electrical Rough-In | 2/10/2005 | 2/11/2005 | 2/11/2005 12:00:00 AM | P | NH |
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 3:43:54 PM. Contact:call stacy ###-#### before you go out or ###-####.
the customer did not call, when i called them they wanted me to wait until they could get there for the inspection. I explained how they could make an appointment and that I could not wait for them. 2/11/2005 3:11:42 PM
|