FIR07-00961
| INSP-Final Inspection | 2/11/2008 | 2/11/2008 | 2/11/2008 5:19:36 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00954
| INSP-Final Inspection | 2/8/2008 | 2/11/2008 | 2/11/2008 2:56:31 PM | A | PASS |
|
|
|
FIR07-00243
| INSP-Final Inspection | 2/8/2008 | 2/11/2008 | 2/11/2008 2:55:44 PM | A | PASS |
|
|
Fire sprinkler system final testing passed, previous correction items are complete, plan resubmittals provided, three defficiencies noted at today's inspection repaired while on site, dry system trip test and DCVA forward flow testing passed. See project related permit FIR06-00727 for the balance of activities and inspections completed for this overhead work listed under the UG permit due to contractor mixing permit #'s for site inspeciton requests.
|
FIR08-00051
| INSP-Sprinkler Rough-in/Hydro | 2/8/2008 | 2/11/2008 | 2/11/2008 2:46:41 PM | A | PART |
|
|
OH rough-in installation passed inspection, see annotations on plan with today's date, hydrostatic testing for this remodel area also completed acceptable.
|
BLD07-00873
| FIRE-Final Inspection | 2/8/2008 | 2/11/2008 | 2/11/2008 11:51:03 AM | A | FAIL |
|
|
Final pending project related fire alarm work to interconnect mag locks at the elevator lobby exit doors to the fire alarm panel and provision of access controled egress components per IFC 2003 1008.1.3.4 items 1-6.
|
FIR08-00090
| INSP-Sprinkler Rough-in/Hydro | 2/8/2008 | 2/11/2008 | 2/11/2008 11:46:13 AM | A | PASS |
|
|
Fire sprinkler modifications are acceptable, inspection passed, permit is okay for final.
|
FIR07-01037
| INSP-Final Inspection | 2/8/2008 | 2/11/2008 | 2/11/2008 11:04:26 AM | A | FAIL |
|
|
Strobe notification devices need to be synchronized per NFPA 72 requirements..
|