Inspections for the day of: Monday, February 11, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00449 INSP-Sprinkler Rough-in2/8/20082/11/20082/11/2008 4:18:26 PMPPASS
The fire proof patching has been completed. Sprinkler piping is ok to cover.
BLD07-02835 FIRE-Final Inspection2/8/20082/11/20082/11/2008 4:16:50 PMPPASS
life safety passed
BLD07-02282 FIRE-Final Inspection2/11/20082/11/20082/11/2008 3:52:24 PMPPASS
LIfe safety passed.
FIR08-00027 INSP-Final Inspection2/8/20082/11/20082/11/2008 2:54:53 PMPPASS
Permit finaled after a set of correct as-builts were provided.
FIR08-00043 INSP-Final Inspection2/8/20082/11/20082/11/2008 2:54:22 PMPPASS
Permit finaled after a set of correct as-builts were provided.
FIR08-00043 INSP-Sprinkler Rough-in2/8/20082/11/20082/11/2008 2:53:47 PMPPASS
Permit finaled after a set of correct as-builts were provided.
FIR08-00027 INSP-Sprinkler Rough-in2/8/20082/11/20082/11/2008 2:53:13 PMPPASS
Permit finaled after a set of correct as-builts were provided.
FIR08-00065 INSP-Sprinkler Rough-in2/8/20082/11/20082/11/2008 1:25:03 PMAFAIL
The tenant space is locked. There is no access. No inspection performed.
FIR07-00697 INSP-Sprinkler Rough-in2/8/20082/11/20082/11/2008 12:50:37 PMPFAIL
Mike wanted me to just inspect the cafeteria today. I found that the pipe sizes as shown on the approved plans for this area do not match what is installed. Infact the unapproved as-builts that the fitter had do not match the installation. No piping is to be covered. Correct as-built plans need to be submitted and approved.
BLD08-00117 FIRE-Final Inspection2/5/20082/11/20082/11/2008 10:00:38 AMAFAIL
Remove the items being stored in the west basement stairwell. Provide sprinkler coverage in the basement at the exit to the west stairwell. Provide verification that the sprinkler pendant located next to the supply diffuser in the open office area of the basement has the required temperature rating as per NFPA 13. Provide verification of emergency lighting for the first floor including the stairs. Provide exit sign in the basement, at/near the interior stairs, veiwable by the basements occupants see IFC 1011. Remove the thumbturn locks on the main exit see IFC 1008.1.8.1. Remove the manual flush bolts on the main exit see IFC 1008.1.8.4. If keyed hardware is installed they shall comply with IFC 1008.1.8.3. Remove the thumbturn from the west basement door. Keyed hardware is not allowed on this door. Comply with IFC1008.1.8.1 and 1008.1.8.4.
FIR06-00011 INSP-Alarm Testing2/8/20082/11/20082/11/2008 8:51:20 AMACANC
brian Phone #: ###-####
BLD06-03160 FIRE-Final Inspection2/8/20082/11/20082/11/2008 8:50:03 AMAFAIL
zane was not here and nobody else knew anything about the inspection. No inspection performed. - fire life safety Phone #: ###-####