Inspections for the day of: Thursday, February 11, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02071 FIRE-Final Inspection2/10/20102/11/20102/12/2010 7:15:04 AMPPASS
Life safety passed. Plans had not been routed through fire, hence the contractor had installed duct smoke detectors as shown on the city approved plans. They however had not been connected to the existing fire alarm system. Due to the hvac units being smaller than 2,000 cfm the duct smoke detectors have been removed.
FIR09-00536 INSP-Sprinkler Rough-in2/11/20102/11/20102/11/2010 3:26:19 PMPCANC
Cancelled due to time constraints and Micron plan review. I spoke to todd and the inspection will be rescheduled for tomorrow.
BLD09-00461 FIRE-Final Inspection2/11/20102/11/20102/11/2010 3:22:03 PMPFAIL
Per the approved drawings and documents the address is 4450. The address of 4420 has been installed on the building. I spoke to April with the addressing dept. and she believes that neither address is correct. I let the contractor know that he needs to speak to April to get the correct address. Also the exit discharge light out of the southeast exit did not work nor did the emergency light just inside of this same door. All other items appear ok.
FIR09-00692 INSP-Final Inspection2/11/20102/11/20102/11/2010 1:13:46 PMPCANC
Cancelled due to too many inspections, time constraints and Micron plan review. Inspection was originally scheduled for this morning but was changed to an afternoon. I spoke to the contractor about performing a morning inspection but he wanted an afternoon inspection. To be rescheduled for tomorrow.
FIR10-00053 INSP-Final Inspection2/11/20102/11/20102/11/2010 12:20:10 PMPPASS
permit finaled
BLD10-00035 FIRE-Final Inspection2/10/20102/11/20102/11/2010 11:27:19 AMAFAIL
Provide the flammable materials storage cabinets as per the city approved plans and provide storage height control as discussed.
BLD09-01219 FIRE-Final Inspection2/11/20102/11/20102/11/2010 11:21:04 AMPPASS
Life safety passed
FIR09-00720 INSP-Final Inspection2/10/20102/11/20102/11/2010 11:20:00 AMPPASS
Permit finaled. Bob Seagler is folowing up on the placement of the map at the facp.
FIR09-00735 INSP-Final Inspection2/10/20102/11/20102/11/2010 11:11:54 AMPPASS
permit finaled
FIR09-00708 INSP-Sprinkler Rough-in/Hydro2/10/20102/11/20102/11/2010 10:24:40 AMAPASS
The overhead hydro test of dry systems 3 and 4 and wet system 1 passed.
BLD09-01866 FIRE-Final Inspection2/9/20102/11/20102/11/2010 9:36:26 AMAFAIL
Provide an annual inspection for both of the fire extinguishers, provide the correct sticker at the main exit as discussed, post address numbers atleast 4" in height and provide passage hardware on the breakroom door since an exit sign is designating this door as an exit path.
FIR09-00716 INSP-Final Inspection2/8/20102/11/20102/11/2010 9:06:46 AMAFAIL
The NetCon was a 7 and the manual pull station had been installed above 48". No other testing was performed.
FIR09-00717 INSP-Final Inspection2/8/20102/11/20102/11/2010 9:06:16 AMAFAIL
The NetCon was a 6 and the manual pull station had been installed above 48". No other testing was performed.
FIR09-00692 INSP-Final Inspection2/9/20102/11/20102/11/2010 7:33:24 AMACANC
I spoke to Tom and he stated that his office shoud be rescheduling for this afternoon.
FIR09-00720 INSP-Final Inspection2/10/20102/11/20102/10/2010 10:13:32 AMACANC
Raef is the contact his no. is ###-####. Inspection requested from web by: Shawna Gates Phone #: ###-#### Inspection cancelled from web by: Shawna Gates