Inspections for the day of: Monday, February 11, 2013.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00255 INSP-Final Inspection2/8/20132/11/20132/11/2013 5:07:02 PMAPART
Items needed for final include; points map with accurate room numbers, correct addresses at SD 60 and 63, revise visual coverage at corridor 145- see red line review comments, install panel batteries per plans. ID and duct detectors not yet tested. Remainder of installation including riser supervision, notification, initiating, monitoring and panel items tested okay.
FIR12-00246 INSP-Final Inspection2/11/20132/11/20132/11/2013 4:54:24 PMPPART
Riser supervision tested satisfactory, low air switch adjusted while on site, forward flow completed.
FIR12-00580 INSP-Final Inspection2/5/20132/11/20132/11/2013 4:49:15 PMPPASS
Scope of fire alarm work finished and passed inspection. Permit finaled.
FIR12-00460 INSP-Final Inspection2/11/20132/11/20132/11/2013 4:48:05 PMPPASS
Hood suppression permit final approved.
FIR13-00056 INSP-Sprinkler Rough-in2/11/20132/11/20132/11/2013 4:45:53 PMAPART
Overhead work at the drop ceilings approved for cover. In rack sprinkler rough-in also completed okay.
BLD12-03263 FIRE-Final Inspection2/6/20132/11/20132/11/2013 12:00:00 AMACANC
Allison-Please call prior to inspection Phone #: ###-####