FIR06-00331
| FIR-Aging Inspection | 2/11/2013 | 2/11/2013 | 2/13/2013 7:46:15 AM | | NR |
|
|
Boise city fire dept is currently working with the owner and contractor on getting this permit finaled.
|
FIR12-00661
| INSP-Final Inspection | 2/11/2013 | 2/11/2013 | 2/11/2013 3:48:36 PM | P | FAIL |
|
|
Project is not ready for a final inspection. The outside alarm bell is located incorrectly and needs to be relocated. It also appears that non-approved tamper switches have been installed on the backflow valves. The tamper switches have not been wired or tested to the fire alarm panel. The fire alarm permit has not been scheduled. Pendant head locations within the building do appear ok.
|
BLD12-03111
| FIRE-Final Inspection | 2/8/2013 | 2/11/2013 | 2/11/2013 2:49:57 PM | A | PASS |
|
|
life safety passed
|