Inspections for the day of: Tuesday, February 11, 2014.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02059 ELE-Aging Inspection2/11/20142/11/20142/12/2014 4:50:10 PM DONE
Waiting on owner
ELE10-02355 ELE-Aging Inspection2/11/20142/11/20142/12/2014 4:36:55 PM DONE
Still under construction
GCE13-00173 GCE-Rough-In2/11/20142/11/20142/11/2014 4:32:52 PMPFAIL
Kevin ###-####, Partial cover & rough-in on south side 330.30- MC cable shall be secured with in 12" of entering boxes
ELE14-00322 Temporary Service2/10/20142/11/20142/11/2014 4:00:34 PMPPASS
If you have any questions, please call out office. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan t/s o/h n ok
GCE14-00020 GCE-Permanent Service2/10/20142/11/20142/11/2014 3:14:29 PMAPASS
Andy ###-#### p/s o/h rec ok
ELE13-02146 Final2/10/20142/11/20142/11/2014 2:46:09 PMPFAIL
Please call Bill ahead at ###-#### for entry. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast 314.20- Boxes in walls constructred of wood shall be flush or employ extension ring. Device shall be secured to box. Down bed.
314.25- All boxes shall have covers. Office smoke detector
ELE13-03559 Final2/11/20142/11/20142/11/2014 2:15:40 PMPPASS
MIKE Phone #: ###-#### Final ok
ELE14-00131 Final2/11/20142/11/20142/11/2014 1:50:21 PMPPASS
Please give me half an hour notice to unsure access thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Final ok
ELE14-00131 Final2/11/20142/11/20142/11/2014 1:49:47 PMPPASS
Please give me half an hour notice to unsure access thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Final ok
ELE14-00307 Electrical Rough-In2/11/20142/11/20142/11/2014 1:35:26 PMPPASS
Phone #: ###-#### >> Inspection requested via web by ron spen cer Walls rough in ok cover
ELE14-00313 Electrical Rough-In2/10/20142/11/20142/11/2014 1:00:29 PMAPART
rough cover for new room, service to follow later. Phone #: ###-#### >> Inspection requested via web by shane vigil 400.8- Flexible cords shall not be ran through walls.
Transformer shall be located in an accessible location. Wall to remain open under basement wall unit. Rest of walls ok cover
ELE14-00092 Conference2/10/20142/11/20142/11/2014 10:10:42 AMADONE
per structural inspector,, Tony,, ###-#### Wiring possibly damaged at top of fireplace chase. Posted correction and contacted contractor to fix
ELE14-00092 Electrical Rough-In2/11/20142/11/20142/11/2014 9:58:26 AMPFAIL
per structural inspector,, Tony,, ###-####
300.4- NM cable shall be protected from physical damage. Top of fireplace chase sheet metal may damage NM cable.
GCE13-00216 GCE-Rough-In Permanent Service2/10/20142/11/20142/11/2014 9:32:31 AMAPASS
Tom ###-#### Rough in ok cover p/s u/g n ok
ELE13-02929 Final2/10/20142/11/20142/11/2014 9:04:32 AMAPASS
Garage code: 3283 Phone #: ###-#### >> Inspection requested via web by daniel bibikov Final ok
ELE14-00324 Electrical Rough-In2/10/20142/11/20142/11/2014 8:37:15 AMAPASS
General Contractor (Gary) will be on site at 7:30 am. Phone #: ###-#### >> Inspection requested via web by David Nelson
2 bathrooms floor heat rough in ok cover
ELE13-03249 Final2/11/20142/11/20142/11/2014 7:21:44 AMACANC
Contact: Frank Yantis Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden