Inspections for the day of: Thursday, February 11, 2016.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00023 INSP-Sprinkler Rough-in2/10/20162/11/20162/11/2016 2:48:42 PMPPASS
Rough to cover inspection for entire house passed/complete, approved for cover. Tenting inspection for 3rd level of house passed/complete, all area's approved for cover.
BLD16-00251 FIRE-Final Inspection2/10/20162/11/20162/11/2016 2:24:49 PMAFAIL
No fire sprinklers, no fire alarms, fire extinguishers inspections tags are current, emergency egress lighting tested/passed. Two exit signs, one on the southeast side and one on the southwest side need to be serviced/repaired. Slide-bolt currently installed on mailroom interior door, slide-bolt must be re moved. Notified point of contact Dane, phone number ###-#### of the multiple thumb-turn deadbolts throughout the facility, informed him that the thumb-turn deadbolts could become an issue for the final building inspection.
FIR16-00045 INSP-Sprinkler Rough-in2/10/20162/11/20162/11/2016 10:19:26 AMAPASS
Underground remote FDC inspection passed/complete, approved for cover.
FIR15-00912 INSP-Supply line flush2/10/20162/11/20162/11/2016 10:00:46 AMAPASS
Underground fire line flush passed/complete.
BLD15-02224 FIRE-Final Inspection2/10/20162/11/20162/10/2016 1:22:49 PMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers have current tags. Life fire safety inspection passed/complete.