Inspections for the day of: Wednesday, February 12, 2003.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00228 INSP-Final Inspection2/7/20032/12/20032/12/2003 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Terry Owsley inspection stopped due to: horns not working on all floors; strobes not in sync; south area of first floor devices not being recognized. Also need device location maps at FACP. Will need to test all devices, notification circuits; troubles; elevator recall; pump supervision - start test from scratch 2/12/2003 8:52:48 AM
BLD00-01894 FIRE-Final Inspection2/11/20032/12/20032/12/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/11/2003 at 8:38:50 AM. Contact: ###-####.
FIR02-00418 INSP-Final Inspection2/11/20032/12/20032/12/2003 12:00:00 AMAPASS
MIKE; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
BLD02-02202 FIRE-Final Inspection2/11/20032/12/20032/12/2003 12:00:00 AMAPASS
###-####
BLD02-02156 FIRE-Conference2/12/20032/12/20032/12/2003 12:00:00 AMPPART
met with GC while doing sprinkler r/i; he wanted to know what is needed for final; need extinguishers and he mentioned the doors to the tenant will be on mag hold opens which will require smoke detection and told him he needed to get plans in for review; he also mentioned that they install a stove to heat soups and pastas and will need mechanical permit 2/12/2003 4:12:38 PM