Inspections for the day of: Thursday, February 12, 2004.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00684 FIR-Aging Inspection2/12/20042/12/20042/12/2004 12:00:00 AM FAIL
I spoke to Ron at Treasure Valley Fire and he stated that he would follow up to see if work has been completed and phone in inspection 2/12/2004 3:32:41 PM
BLD02-03053 FIRE-Final Inspection2/10/20042/12/20042/12/2004 12:00:00 AMAFAIL
provide duct smoke detectors for unit shut down on both units 2/12/2004 10:23:23 AM
BLD03-00261 FIRE-Final Inspection2/10/20042/12/20042/12/2004 12:00:00 AMAPASS
fire life safety finaled 2/12/2004 10:23:42 AM
BLD03-01797 FIRE-Conference2/11/20042/12/20042/12/2004 12:00:00 AMAPART
Temporary occupancy was given until all of the fire mains are upgraded per plans submitted to boise city and the fire alarm system is completed. Curbing needs to be painted and existing exits signs repaired 2/12/2004 9:58:10 AM
MIS04-00053 FIR-Final2/11/20042/12/20042/12/2004 12:00:00 AMAPASS
Fire life safety finaled 2/12/2004 8:17:04 AM
FIR03-00806 INSP-Final Inspection2/12/20042/12/20042/12/2004 12:00:00 AMAPART
Temporary occupancy was given until all of the fire mains are upgraded per plans submitted to boise city and the fire alarm system is completed
FIR04-00021 INSP-Final Inspection2/12/20042/12/20042/12/2004 12:00:00 AMAPART
Temporary occupancy was given until all of the fire mains are upgraded per plans submitted to boise city and the fire alarm system is completed
FIR03-00570 INSP-Final Inspection2/5/20042/12/20042/12/2004 12:00:00 AMAPASS
fire alarm finaled 2/12/2004 12:36:07 PM
MIS04-00045 FIR-Final2/9/20042/12/20042/12/2004 12:00:00 AMPPASS
Fire life safety finaled 2/12/2004 12:50:45 PM
BLD02-00410 FIRE-Conference2/12/20042/12/20042/12/2004 12:00:00 AMPFAIL
I spoke to Rob Bailey at Mountain Alarm about getting their alarm permit finaled. He said it will be called in next week 2/12/2004 4:06:45 PM
FIR03-00764 INSP-Final Inspection2/12/20042/12/20042/12/2004 12:00:00 AMPPASS
office; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
BLD03-01135 FIRE-Final Inspection2/12/20042/12/20042/12/2004 12:00:00 AMPFAIL
Door hardware issues still need addressed. Provide labels on the electrical panels. Provide map at the facp annunciator. Provide "No Parking - Fire Lane" text on red curbing
FIR03-00639 INSP-Final Inspection2/12/20042/12/20042/12/2004 12:00:00 AMPPASS
fire sprinklers finaled
FIR03-00448 INSP-Sprinkler Rough-in/Hydro2/11/20042/12/20042/12/2004 12:00:00 AMPFAIL
Sprinkler rough-in on the first floor is ok. Insulation inspection is needed before covering can be done.
Sprinkler rough-in on the second floor is ok except for hangers and supports are needed for the plastic piping mains. Also verification is needed that the piping changes to the rise up to the second floor do not adversely affect the hydraulic calculations 2/12/2004 3:24:10 PM
FIR03-00715 INSP-Final Inspection2/12/20042/12/20042/12/2004 12:00:00 AMPCANC
dan ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR04-00044 INSP-Conference2/12/20042/12/20042/12/2004 12:00:00 AMPPART
inspection was for hanger attachments. attachments okay 2/12/2004 4:25:14 PM
FIR04-00044 INSP-Conference2/12/20042/12/20042/12/2004 12:00:00 AMPPART
inspection was for hanger attachments. attachments okay 2/12/2004 4:25:14 PM
FIR04-00024 INSP-Sprinkler Rough-in2/12/20042/12/20042/12/2004 12:00:00 AMPPART
underground supply piping is ok to cover. 2/12/2004 2:48:19 PM