Inspections for the day of: Monday, February 12, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-02089 Final2/12/20072/12/20072/12/2007 4:25:37 PMPPASS
all work now will be done on ele07-00461
ELE04-01035 Final2/12/20072/12/20072/12/2007 4:23:26 PMPPASS
all work now done on ele07-00461
ELE07-00461 Final2/9/20072/12/20072/12/2007 4:11:59 PMPFAIL
Neil ###-#### corr. called 300.4(D) 11/4" for cables parallel to studs, 314.16 box fill 5 locations, 334.30&314.17 staple cables within 8" of plastic boxes, 314.29 ceiling box sahll be accessible needs mud ring west half of basement, 210.70 (A)(2)(c) needs 3way for stairs
ELE06-04320 Final2/12/20072/12/20072/12/2007 3:10:24 PMPPASS
Pleae call for entry access Phone #: ###-#### ok survey 210.8 needs power to gfci outside recept called
ELE07-00092 Permanent Service2/12/20072/12/20072/12/2007 2:11:51 PMPFAIL
john; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. called 250.24(A)(1) shall terminate GEC too neutral bus and all neutrals too neutral bus
ELE07-00081 Rough-In Permanent Service2/12/20072/12/20072/12/2007 1:25:59 PMPPART
Rough In - Service Contact Rick ###-####
Project will be ready for inspection immediately after lunch Phone #: ###-#### r/i p/s o/h rec. ok
ELE06-04410 Electrical Rough-In2/9/20072/12/20072/12/2007 12:32:05 PMAPART
steve - ceiling; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
2nd floor grid ceilings ok
ELE07-00362 Final2/9/20072/12/20072/12/2007 11:12:33 AMAPART
brad; Phone #: ###-#### Internet Inspection Request from: Victoria Beall needs listing for new sander, and address cords as fixed wiring
ELE06-04335 Electrical Rough-In2/8/20072/12/20072/12/2007 10:35:03 AMAPART
William ; Phone #: ###-#### Internet Inspection Request from: Darla Downs
r/i ok still needs makeup
ELE06-03280 Electrical Rough-In2/9/20072/12/20072/12/2007 10:02:41 AMAPART
Please inspect partial 1st floor of D-wing. Thank you. Phone #: ###-#### ok looked at room they mocked up only conference
ELE06-02704 Electrical Rough-In2/9/20072/12/20072/12/2007 10:01:26 AMAPART
Please inspect 3rd floor and partial attic in C-wing. Thank you. Phone #: ###-#### ok anop
ELE06-03952 Final2/9/20072/12/20072/12/2007 8:37:06 AMAPASS
greg ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok