Inspections for the day of: Tuesday, February 12, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01669 DOC - Permit Expired2/12/20082/12/20082/12/2008 4:18:30 PMPPASS
looked for sign, other type business in assigned location, no sign as permitted
ELE04-03885 DOC - Permit Expired2/12/20082/12/20082/12/2008 3:23:57 PMPPASS
looked at sign, new business now located there with new sign, did not see old sign
ELE07-03075 Final2/12/20082/12/20082/12/2008 3:03:42 PMPPASS
looked at sign, ok to final
ELE08-00294 Permanent Service2/12/20082/12/20082/12/2008 2:25:59 PMPPASS
Meter is marked just waiting for ok to conect. Any question please call thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig p/s, exst meter pak, n, ok
ELE08-00257 Rough-In Permanent Service2/11/20082/12/20082/12/2008 1:28:30 PMPCANC
calvin Phone #: ###-#### see ri
ELE08-00257 Electrical Rough-In2/12/20082/12/20082/12/2008 1:28:03 PMPPART
calvin Phone #: ###-#### ri ok inside building only, need to see u/g for concrete encased electrode for service
ELE08-00339 Rough-In Permanent Service2/12/20082/12/20082/12/2008 12:53:28 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left correction notice, BCC approved set of plans shall be on job, address shall be posted, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
ELE08-00325 Electrical Rough-In2/11/20082/12/20082/12/2008 10:18:42 AMAPASS
mark - please call 1/2 hr prior to inspection Phone #: ###-#### called contractor, ric ok
ELE07-02770 Final2/11/20082/12/20082/12/2008 10:02:56 AMAPASS
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok to final
ELE07-03564 Final2/12/20082/12/20082/12/2008 9:32:34 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok to final, signed occupancy card, met electrician
ELE08-00331 Temporary Service2/11/20082/12/20082/12/2008 8:52:22 AMAFAIL
alan Phone #: ###-#### called, left correction notice, BCC job id sticker shall be posted, NEC 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A) gec shall connect to grounded service conductor, fee due
ELE08-00292 Electrical Rough-In2/11/20082/12/20082/12/2008 8:10:50 AMAPASS
trent Phone #: ###-#### ric baths only ok