BLD07-00052
| FIRE-Final Inspection | 2/12/2008 | 2/12/2008 | 2/15/2008 2:01:24 PM | P | PASS |
|
|
Fire life safety passed.
|
FIR07-01035
| INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/13/2008 2:46:56 PM | P | PASS |
|
|
Fire alarm testing passed inspection after corrections made while on site, field modifications are acceptable, permit finaled.
|
FIR06-00365
| INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/13/2008 9:59:44 AM | P | PART |
|
|
1st floor walkthrough of the apartment units only -noted 401's have been added at various locations to avoid light fixture obstructions, painted heads indicated at the previous visit have been replaced as necessary.
|
FIR07-01054
| INSP-Sprinkler Rough-in | 2/12/2008 | 2/12/2008 | 2/13/2008 9:32:56 AM | P | DEFR |
|
|
Duplicate inspection request.
|
BLD07-03076
| FIRE-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 3:26:49 PM | P | PASS |
|
|
Functional testing of the new door hardware passed inspection.
|
BLD06-00456
| FIRE-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 2:51:48 PM | A | PART |
|
|
Fire life safety final pending fire department access lane curb marking per fire code review notes and provision of missing max. occupant load signs at three areas (pool room, patio area, exercise room) -see review notes for details. Remainder of fire life safety is satisfactory.
|
FIR06-00727
| INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 1:51:52 PM | P | PASS |
|
|
UG fire supply line permit finaled.
|
BLD07-00095
| FIRE-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 1:30:27 PM | P | PASS |
|
|
Life safety finaled.
|
FIR07-00759
| FIR-Aging Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 1:01:55 PM | P | DEFR |
|
|
Work in progress to amend items on the correction notice issued 12/28/07.
|
FIR06-00985
| INSP-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 12:59:42 PM | A | FAIL |
|
|
Need to remove travel caps and install escutcheons at each sprinkler head in the mechanical closets per unit.
|
FIR06-00986
| INSP-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 12:56:42 PM | A | FAIL |
|
|
Need to remove travel caps and install escutcheons at each sprinkler head in the mechanical closets per unit.
|
FIR08-00092
| INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 12:54:16 PM | P | PASS |
|
|
The scope of work per permit documents has been verified for completion, fire sprinkler permit finaled.
|
FIR08-00029
| INSP-Sprinkler Rough-in | 2/11/2008 | 2/12/2008 | 2/12/2008 12:52:27 PM | A | PART |
|
|
OH fire sprinkler modifications are approved for cover at the drop ceilings, noted four painted escutcheons at the hard lid area concealed heads to be replaced prior to final permit approval.
|
FIR07-00662
| INSP-Final Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 8:39:16 AM | A | PASS |
|
|
Fire alarm work passed final inspection, permit finaled.
|
FIR07-00910
| FIR-Aging Inspection | 2/12/2008 | 2/12/2008 | 2/12/2008 8:34:32 AM | | DEFR |
|
|
Under construction, no call for field inspection to date.
|