BLD08-01951
| FIRE-Final Inspection | 2/12/2009 | 2/12/2009 | 2/17/2009 8:06:17 AM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD08-02487
| FIRE-Final Inspection | 2/12/2009 | 2/12/2009 | 2/13/2009 12:52:26 PM | P | NR |
|
|
Pending project related fire sprinkler permit work.
|
FIR08-00103
| INSP-Alarm Testing | 2/11/2009 | 2/12/2009 | 2/12/2009 4:39:45 PM | A | PART |
|
|
Discussed plan resubmittals due to modifications including 13 added SD for dampers in the common corridors, added heat and smoke detectors in the elevator hoistway, relay for the mag locks at the main lobby doors, changes in the matrix for unused CR at the elevator smoke doors. Walkthrough for the basement level parking garage completed-noted one overspaced area at a handicap accessible parking space. Discussed project inspection schedule, also need to provide list of signals recieved during pre-testing.
|
FIR08-00783
| INSP-Final Inspection | 2/11/2009 | 2/12/2009 | 2/12/2009 4:34:57 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR08-00766
| INSP-Sprinkler Rough-in/Hydro | 2/12/2009 | 2/12/2009 | 2/12/2009 2:55:12 PM | P | NR |
|
|
Missing thrust blocks, seismic clearance at the riser SW corner is not sufficient, bolts at mech. tees and 90's need coated and covered.
|
FIR07-00928
| INSP-Sprinkler Rough-in/Hydro | 2/11/2009 | 2/12/2009 | 2/12/2009 2:01:46 PM | A | PART |
|
|
6th floor overhead hydrostatic test passed.
|
BLD09-00005
| FIRE-Final Inspection | 2/11/2009 | 2/12/2009 | 2/12/2009 2:00:10 PM | A | PASS |
|
|
Fire life safety final inspection passed.
|
BLD08-01099
| FIRE-Final Inspection | 2/11/2009 | 2/12/2009 | 2/12/2009 11:49:06 AM | A | PASS |
|
|
Life safety finaled.
|
FIR08-00815
| INSP-Sprinkler Rough-in/Hydro | 2/11/2009 | 2/12/2009 | 2/12/2009 11:48:33 AM | A | PART |
|
|
Okay to cover overhead install with the exception of three locations including first floor water closet where tenting is inadequate for the sprinkler drop, head adjacent to the basement spiral stairway not yet installed, and an overspaced pendent head at a basement bedroom. Remainder of correction items noted on 2/11 repaired. Contractor to maintain adequate cold cavity protection throughout the attic spaces.
|