Inspections for the day of: Friday, February 12, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00123 FIRE-Final Inspection2/11/20102/12/20102/16/2010 7:31:19 AMACANC
Rescheduled for tuesday due to time constraints.
FIR09-00733 INSP-Final Inspection2/11/20102/12/20102/12/2010 3:30:10 PMPCANC
Cancel per Tom. To be rescheduled for tuesday.
BLD09-01717 FIRE-Final Inspection2/11/20102/12/20102/12/2010 3:01:49 PMADEFR
A life safety inspection is not required for this residential permit.
FIR10-00046 INSP-Final Inspection2/12/20102/12/20102/12/2010 3:00:18 PMPPASS
Permit finaled. Sync modules were installed and setup while I waited. I let Tom know that I would need as-builts showing the addition of the sync modules.
BLD09-01742 FIRE-Final Inspection2/11/20102/12/20102/12/2010 2:55:46 PMACANC
The project related fire alarm permit needs to be finaled and the exit signs/emergency lighting inspected. Other life safety items have been verified.
FIR09-00692 INSP-Final Inspection2/12/20102/12/20102/12/2010 2:54:29 PMPFAIL
The heat detectors in the garage need to be mounted at the ceiling as discussed, the a/v needs to be relocated within 15' of the end of the corridor, the NAC panel does not report trouble signals to the FACP. No devices have been tested or the a/v's activated and the interconnection between the NAC and the existing FACP has not been verified.
BLD09-01411 FIRE-Final Inspection2/12/20102/12/20102/12/2010 11:51:51 AMPPASS
Life safety passed
BLD10-00192 FIRE-Final Inspection2/12/20102/12/20102/12/2010 11:51:06 AMAPASS
Life safety passed
FIR09-00708 INSP-Sprinkler Rough-in2/11/20102/12/20102/12/2010 11:46:35 AMAPASS
See the city approverd plans for locations with todays date for piping inspected. I The inspection included both wet and dry systems.
BLD10-00192 BLD-Final2/11/20102/12/20102/12/2010 9:40:35 AMAPASS
Life safety passed
BLD09-02261 FIRE-Final Inspection2/11/20102/12/20102/12/2010 9:40:11 AMAPASS
Life safety passed. The contractor is installing a baffle between the two sprinkler pendants that are located too close to one another. The smoke evacuation system tested ok.
BLD09-01866 FIRE-Final Inspection2/11/20102/12/20102/12/2010 8:27:51 AMAPASS
Life safety passed
FIR09-00692 INSP-Final Inspection2/11/20102/12/20102/12/2010 8:09:57 AMAFAIL
No testing performed this morning since the electrician is still wiring up the panel and is having trouble finding the EOL on the door circuit.