BLD08-00123
| FIRE-Final Inspection | 2/11/2010 | 2/12/2010 | 2/16/2010 7:31:19 AM | A | CANC |
|
|
Rescheduled for tuesday due to time constraints.
|
FIR09-00733
| INSP-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 3:30:10 PM | P | CANC |
|
|
Cancel per Tom. To be rescheduled for tuesday.
|
BLD09-01717
| FIRE-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 3:01:49 PM | A | DEFR |
|
|
A life safety inspection is not required for this residential permit.
|
FIR10-00046
| INSP-Final Inspection | 2/12/2010 | 2/12/2010 | 2/12/2010 3:00:18 PM | P | PASS |
|
|
Permit finaled. Sync modules were installed and setup while I waited. I let Tom know that I would need as-builts showing the addition of the sync modules.
|
BLD09-01742
| FIRE-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 2:55:46 PM | A | CANC |
|
|
The project related fire alarm permit needs to be finaled and the exit signs/emergency lighting inspected. Other life safety items have been verified.
|
FIR09-00692
| INSP-Final Inspection | 2/12/2010 | 2/12/2010 | 2/12/2010 2:54:29 PM | P | FAIL |
|
|
The heat detectors in the garage need to be mounted at the ceiling as discussed, the a/v needs to be relocated within 15' of the end of the corridor, the NAC panel does not report trouble signals to the FACP. No devices have been tested or the a/v's activated and the interconnection between the NAC and the existing FACP has not been verified.
|
BLD09-01411
| FIRE-Final Inspection | 2/12/2010 | 2/12/2010 | 2/12/2010 11:51:51 AM | P | PASS |
|
|
Life safety passed
|
BLD10-00192
| FIRE-Final Inspection | 2/12/2010 | 2/12/2010 | 2/12/2010 11:51:06 AM | A | PASS |
|
|
Life safety passed
|
FIR09-00708
| INSP-Sprinkler Rough-in | 2/11/2010 | 2/12/2010 | 2/12/2010 11:46:35 AM | A | PASS |
|
|
See the city approverd plans for locations with todays date for piping inspected. I The inspection included both wet and dry systems.
|
BLD10-00192
| BLD-Final | 2/11/2010 | 2/12/2010 | 2/12/2010 9:40:35 AM | A | PASS |
|
|
Life safety passed
|
BLD09-02261
| FIRE-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 9:40:11 AM | A | PASS |
|
|
Life safety passed. The contractor is installing a baffle between the two sprinkler pendants that are located too close to one another. The smoke evacuation system tested ok.
|
BLD09-01866
| FIRE-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 8:27:51 AM | A | PASS |
|
|
Life safety passed
|
FIR09-00692
| INSP-Final Inspection | 2/11/2010 | 2/12/2010 | 2/12/2010 8:09:57 AM | A | FAIL |
|
|
No testing performed this morning since the electrician is still wiring up the panel and is having trouble finding the EOL on the door circuit.
|