ELE14-00313
| Electrical Rough-In | 2/12/2014 | 2/12/2014 | 2/12/2014 4:13:21 PM | P | PASS |
|
|
Heat unit xfmr reinspect Phone #: ###-#### >> Inspection requested via web by shane vigil Split system transformer and line volt flexible cord moved to interiior of wall unit. Rough in ok cover
|
ELE14-00346
| Electrical Rough-In | 2/12/2014 | 2/12/2014 | 2/12/2014 3:40:11 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspecti Bed multi-wire branch circuit feeders for bedrooms not accessible. Arc fault not required. Some work done in every room. Rough in ok cover
|
ELE13-02146
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 3:10:57 PM | P | PASS |
|
|
Corrections have been made. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Final ok
|
ELE13-02874
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 2:29:37 PM | P | FAIL |
|
|
Donald PLEASE call before going out Phone #: ###-#### All receptical outlets shall be tamper resistant type. Type UF cable shall be protected from physical damage. All bed outlets shall be AFCI protected. LT and switch. Reverse polarity in bed
|
ELE14-00334
| Permanent Service | 2/11/2014 | 2/12/2014 | 2/12/2014 1:43:10 PM | P | PASS |
|
|
Please call Clay when on your way, ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s o/h rec ok
|
GCE14-00021
| GCE-Rough-In | 2/11/2014 | 2/12/2014 | 2/12/2014 1:35:44 PM | A | PASS |
|
|
Pat ###-#### Kitchen remodel rough in ok cover
|
ELE13-03566
| Final | 2/12/2014 | 2/12/2014 | 2/12/2014 12:54:38 PM | P | FAIL |
|
|
final inspection Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe No access to interior. 210.23(A)(2)- Equiptment fastened in place shall not exceed 50% of branch circuit rating. Future vacuum
|
ELE14-00039
| Final | 2/6/2014 | 2/12/2014 | 2/12/2014 11:44:34 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot 110.3- Complete wiring. Open ground on several receptical outlets in east bedrooms in basement
|
ELE14-00183
| Final | 2/12/2014 | 2/12/2014 | 2/12/2014 9:43:43 AM | A | PASS |
|
|
Contact: Justin Hugo Phone #: ###-#### >> Inspection requested via web by Deb Gooden Final ok
|
ELE13-03249
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 9:33:20 AM | A | PASS |
|
|
Contact: Frank Yantis Phone #: ###-#### >> Inspection requested via web by Deb Gooden Non listed fixtures removed or replaced with listed fixtures, corrections done. Final ok
|
GCE14-00022
| GCE-Rough-In | 2/11/2014 | 2/12/2014 | 2/12/2014 8:48:45 AM | A | PASS |
|
|
Aaron ###-#### Service not complete. House rough in ok cover
|
ELE14-00333
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 8:11:45 AM | P | CANC |
|
|
Someone will be there Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan
|
ELE14-00333
| Electrical Rough-In | 2/11/2014 | 2/12/2014 | 2/12/2014 8:11:40 AM | P | CANC |
|
|
Someone will be there Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan
|
ELE13-02675
| Final | 2/11/2014 | 2/12/2014 | 2/11/2014 3:00:28 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast Final ok
|