ELE12-01645
| ELE-Aging Inspection | 2/12/2014 | 2/12/2014 | 2/20/2014 2:20:24 PM | | DONE |
|
|
see final
|
ELE12-00227
| ELE-Aging Inspection | 2/12/2014 | 2/12/2014 | 2/13/2014 12:10:27 PM | | DONE |
|
|
still under construction
|
ELE13-03157
| Electrical Rough-In | 2/12/2014 | 2/12/2014 | 2/12/2014 4:49:59 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender Rough-in ok cover 5 bay garage
|
ELE12-01237
| ELE-Aging Inspection | 2/12/2014 | 2/12/2014 | 2/12/2014 4:39:29 PM | | DONE |
|
|
Contractor said he would call for final after checking job
|
ELE13-03136
| Final | 2/12/2014 | 2/12/2014 | 2/12/2014 3:18:53 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Dustin Kuester NEC 310.8(C) NM cable not rated for wet locations, Outdoor unit wiring
|
ELE14-00338
| Permanent Service | 2/12/2014 | 2/12/2014 | 2/12/2014 2:50:46 PM | P | PASS |
|
|
vacant Lock Box Door Code 2042 >> Inspection requested via web by Dan Hobdey p/s u/g rec ok
|
ELE14-00052
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 2:23:13 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by JENNY EMEL final ok
|
ELE13-03187
| Final | 2/12/2014 | 2/12/2014 | 2/12/2014 2:01:46 PM | P | PASS |
|
|
CJ is contact. Thanks Phone #: ###-#### >> Inspection requested via web by Chris Chesnut Listed hand held x-ray equipment final ok
|
GCE13-00204
| GCE-Final | 2/12/2014 | 2/12/2014 | 2/12/2014 1:14:02 PM | P | FAIL |
|
|
Terry ###-#### NEC 210.8(A)(1) All 15 and 20 ampere receptacles in the bathroom require GFCI protection Steamer connection not completed, nor GFCI protected
|
ELE14-00126
| Electrical Rough-In | 2/11/2014 | 2/12/2014 | 2/12/2014 10:42:20 AM | A | PART |
|
|
Jake Phone #: ###-#### partial rough-in ok cover walls, area B
|
ELE14-00302
| Electrical Rough-In | 2/11/2014 | 2/12/2014 | 2/12/2014 9:52:45 AM | A | PASS |
|
|
Please call Stephanie ###-#### to meet you there. Thank you. Phone #: ###-#### >> Inspection requested via web by Clay Morgan rough-in ok cover
|
ELE14-00331
| Permanent Service | 2/11/2014 | 2/12/2014 | 2/12/2014 9:30:55 AM | A | FAIL |
|
|
Idaho Power Reconnect. The back slider door is unlocked. Or if there is a lock box on it the code is 7293 Phone #: ###-#### >> Inspection requested via web by Eric Schroeder NEC 110.26(A) working clearance for service meter. Clear vegetation near service meter NEC 250.56 Verify water pipe bond, provide 2-8ft grounding electrodes.
|
ELE13-03105
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 8:53:54 AM | A | PASS |
|
|
wall 18 Phone #: ###-#### >> Inspection requested via web by matt miller rough-in ok pour wall #18
|
ELE13-03341
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 8:38:12 AM | A | PASS |
|
|
Jim Phone #: ###-#### corredtions done final ok
|
ELE14-00192
| Final | 2/11/2014 | 2/12/2014 | 2/12/2014 8:16:22 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk final ok
|
ELE14-00331
| Permanent Service | 2/11/2014 | 2/12/2014 | 2/11/2014 12:03:56 PM | A | CANC |
|
|
Idaho Power Reconnect Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|