Inspections for the day of: Thursday, February 12, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00034 ELE-Aging Inspection2/12/20152/12/20152/12/2015 3:32:45 PM DONE
Markwill call it in
ELE14-03123 Final2/12/20152/12/20152/12/2015 3:24:05 PMPPASS
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt final ok
ELE15-00312 Final2/12/20152/12/20152/12/2015 3:03:31 PMPPASS
Fitness room final Phone #: ###-#### Inspection requested via web by Chris Chesnut final ok
ELE15-00370 Electrical Rough-In2/11/20152/12/20152/12/2015 2:21:24 PMPNH
Phone #: ###-#### Inspection requested via web by Randy Fletcher no access to loadcenter feeding hand dryers in Macys bathroom. Need facilities tech and electrician here to show lockoffs on breakers.
GCE15-00023 GCE-Rough-In2/11/20152/12/20152/12/2015 1:46:27 PMPCANC
Same Day Elec. ###-#### needed p/s 250.53(2) supplemental grounding electrode required. 250.94-Intersystem bonding ground bar required. Will look for this at p/s request and final
GCE15-00019 GCE-Rough-In2/12/20152/12/20152/12/2015 1:17:58 PMPPASS
Bill ###-#### - groundwork inspection request u.ground insp. ok to 2 greenhouse panels
ELE15-00223 Rough-In Permanent Service2/11/20152/12/20152/12/2015 11:07:44 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI r/i ok p/s u/g n ok SERVICE ALREADY ENERGIZED??
ELE13-01291 Electrical Rough-In2/11/20152/12/20152/12/2015 11:05:52 AMAPASS
Cantact Brandon Robinson for level 4 ceiling inspection. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok level 4 elevator lobby ceiling
ELE15-00220 Final2/11/20152/12/20152/12/2015 9:27:42 AMAPASS
The breaker ties are installed on the multi-branch circuits and are ready for inspection, the ACCESS CODE is 1040, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren corrections made final ok
ELE14-03205 Electrical Rough-In2/11/20152/12/20152/12/2015 9:09:34 AMAPASS
Ceiling inspection Phone #: ###-#### Inspection requested via web by Bryan Atkins r/i t bar ceilings ok
ELE14-02710 Electrical Rough-In2/11/20152/12/20152/12/2015 8:52:05 AMAPASS
underground and uffer fix. Phone #: ###-#### Inspection requested via web by Thomas Jenkins r/i u.ground east outside slab ok. Look for #4 ufer on next insp. to bldg. footing