Inspections for the day of: Monday, February 12, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00296 FIR-Aging Inspection2/12/20182/12/20182/16/2018 11:00:14 AM NR
Waiting on the city of boise.
BLD17-03534 FIRE-Final Inspection2/12/20182/12/20182/12/2018 1:21:23 PMPFAIL
Provide address facing the street, repair the non-functioning exit signs/emergency lights, provide emergency lighting at the exit and exit discharge light as per approved plans.

Phone #: ###-#### Inspection requested via web by Don Steinke
FIR17-00412 INSP-Sprinkler Rough-in2/12/20182/12/20182/12/2018 1:08:30 PMPPASS
Underground hydro test passed. Undergrond flush passed. I performed a walk through for a rough-in but not quite ready yet.
NAF17-00058 INSP-Final2/9/20182/12/20182/12/2018 1:07:14 PMPDONE
life safety passed
FIR17-00576 INSP-Sprinkler Rough-in2/12/20182/12/20182/12/2018 12:21:55 PMPPASS
The sprinkler piping in the Conference room with the clouds can be covered. Concealer heads have been added in the clouds to provide floor covereage.
FIR18-00057 INSP-Supply line flush2/9/20182/12/20182/12/2018 11:09:22 AMACANC
Wrong permit number scheduled
FIR18-00057 INSP-Sprinkler Rough-in/Hydro2/9/20182/12/20182/12/2018 11:09:02 AMACANC
Wrong permit number scheduled.
FIR18-00057 INSP-Sprinkler Rough-in2/9/20182/12/20182/12/2018 10:28:47 AMPCANC
Mike Martin is the contact for this inspection. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD16-01757 FIRE-Final Inspection2/9/20182/12/20182/12/2018 10:16:27 AMAFAIL
Project is not ready for a final yet. Todays inspection was just to verify that the exit signs, emergency lights and exit discharge lights functioned on emergency generator. I noted that the exit discharge lights have been connected to photo cells for control. I have contacted plan review since I do not see this allowed in the Code.

Steve Phone #: ###-####