Inspections for the day of: Friday, February 13, 2004.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00649 FIR-Aging Inspection2/13/20042/13/20042/13/2004 12:00:00 AM PASS
Talkked to Greg and he will schedule for an inspection 2/17/2004 1:28:03 PM
BLD03-02647 BLD-Final2/13/20042/13/20042/13/2004 12:00:00 AMAPASS
BLD03-02287 FIRE-Final Inspection2/13/20042/13/20042/13/2004 12:00:00 AMADONE
not a final but a conference to determine GC procedure for working in stairwell - the stairwell will be maintained during construction 2/13/2004 4:05:46 PM
MIS03-00244 FIR-Final2/12/20042/13/20042/13/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
MIS03-00245 FIR-Final2/12/20042/13/20042/13/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD03-02649 FIRE-Final Inspection2/12/20042/13/20042/13/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD03-02648 FIRE-Final Inspection2/12/20042/13/20042/13/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
MIS03-00246 FIR-Final2/12/20042/13/20042/13/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00210 INSP-Alarm Testing2/12/20042/13/20042/13/2004 12:00:00 AMPPASS
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00210 INSP-Alarm Testing2/12/20042/13/20042/13/2004 12:00:00 AMPPASS
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00353 INSP-Alarm Testing2/12/20042/13/20042/13/2004 12:00:00 AMPPASS
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00353 INSP-Alarm Testing2/12/20042/13/20042/13/2004 12:00:00 AMPPASS
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00771 INSP-Alarm Testing2/12/20042/13/20042/13/2004 12:00:00 AMPPASS
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00771 INSP-Alarm Testing2/12/20042/13/20042/13/2004 12:00:00 AMPPASS
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
BLD03-02969 FIRE-Final Inspection2/13/20042/13/20042/13/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/13/2004 at 11:00:17 AM. Contact: ###-####.
BLD03-02876 FIRE-Final Inspection2/13/20042/13/20042/13/2004 12:00:00 AMPPART
fire/life safety will be on temp per Sam Rogers pending completion of the fire alarms 2/13/2004 4:10:06 PM
FIR03-00211 INSP-Final Inspection2/13/20042/13/20042/13/2004 12:00:00 AMPFAIL
Cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino mixing QR heads with standard response; heads not within 22 inches of deck in service aisle; two heads within 6 ft of each area in fab 2/13/2004 4:12:01 PM
FIR04-00059 INSP-Sprinkler Rough-in2/13/20042/13/20042/13/2004 12:00:00 AMPPART
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie okay to cover; tenting completed; riser not complete; a head was added in the living room to prevent overspacing 2/13/2004 4:08:18 PM