Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01188 FIRE-Final Inspection2/10/20062/13/20062/14/2006 9:10:49 AMPPASS
Life safety finaled. Fire doors operated correctly. Per Sam the links on the stage sides only are ok.
FIR05-00755 INSP-Conference2/13/20062/13/20062/13/2006 4:36:06 PMPDONE
I spoke to Linda about moving the project along. She said that she is being held up by the building owner.
BLD05-02947 FIRE-Final Inspection2/13/20062/13/20062/13/2006 3:18:38 PMPPASS
life safety finaled
FIR06-00021 INSP-Sprinkler Rough-in/Hydro2/10/20062/13/20062/13/2006 2:51:52 PMPPASS
Sprinkler piping is ok to cover.
FIR05-00676 INSP-Alarm Testing2/13/20062/13/20062/13/2006 2:07:06 PMPPASS
Fire alarm finaled
FIR05-00724 INSP-Sprinkler Rough-in/Hydro2/10/20062/13/20062/13/2006 12:24:02 PMPPASS
Sprinkler piping is ok to cover. Per contractor the sprinkler head that is missing in the closet will not be required since shelving extends to the door. To be verified when installed.
FIR06-00015 INSP-Final Inspection2/10/20062/13/20062/13/2006 12:22:58 PMAFAIL
Both of the fryers extend outside of both kitchen hoods, the manual pull station is to be mounted between 10' and 20' from the hood in a path of egress. A steamer is being used that does not incorporate a type II hood. Suppression system operated correctly when tested.
BLD06-00087 FIRE-Final Inspection2/10/20062/13/20062/13/2006 10:26:10 AMAPASS
Life safety finaled