Inspections for the day of: Tuesday, February 13, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00467 Electrical Rough-In2/13/20072/13/20072/14/2007 8:44:27 AMPFAIL
curtis - after 2:00 please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith thought ok, but not. Called contr, left message, nec 517.13(A) and (B) metal sheath assembly shall itself qualify as an equipment grounding return path in accordance with 250-118, equipment grounding conductor shall be part of branch circuit of listed cable
ELE07-00459 Permanent Service2/13/20072/13/20072/13/2007 3:24:08 PMPNR
hp; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr, told wrong address and meter not labelled, said to get bld and address to match
ELE07-00445 Electrical Rough-In2/13/20072/13/20072/13/2007 2:49:05 PMPNR
would like cover for basememt family room,bathroom and hallway. Phone #: ###-#### met contr, he still had several items to do, said to call for am
ELE05-04325 Final2/13/20072/13/20072/13/2007 1:57:04 PMPPART
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia 2nd floor, south part anop ok to final
ELE07-00493 Conference2/12/20072/13/20072/13/2007 10:26:42 AMADONE
marc ###-#### talked about new service and what would be required for grounding and clearances
ELE07-00250 Final2/12/20072/13/20072/13/2007 9:35:35 AMAPASS
keith; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, no card to sign
ELE07-00323 Permanent Service2/12/20072/13/20072/13/2007 9:02:00 AMAPASS
Scheduled by a contractor via Hello! on 2/12/2007 at 4:54:45 PM. Contact: ###-####. called contr to id gnd conductor, p/s, exst meter pak, n, ok
ELE06-00113 Final2/12/20072/13/20072/13/2007 8:31:05 AMAPASS
Contact: Greg Pack Phone #: ###-#### corrections made, did not sign occ card since outstanding correction for elevator, ok to final
ELE06-03591 Final2/12/20072/13/20072/12/2007 5:27:42 PMPCANC
Scheduled by a contractor via Hello! on 2/12/2007 at 5:16:38 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 12 2007 5:27PM.