ELE07-00467
| Electrical Rough-In | 2/13/2007 | 2/13/2007 | 2/14/2007 8:44:27 AM | P | FAIL |
|
|
curtis - after 2:00 please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith thought ok, but not. Called contr, left message, nec 517.13(A) and (B) metal sheath assembly shall itself qualify as an equipment grounding return path in accordance with 250-118, equipment grounding conductor shall be part of branch circuit of listed cable
|
ELE07-00459
| Permanent Service | 2/13/2007 | 2/13/2007 | 2/13/2007 3:24:08 PM | P | NR |
|
|
hp; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr, told wrong address and meter not labelled, said to get bld and address to match
|
ELE07-00445
| Electrical Rough-In | 2/13/2007 | 2/13/2007 | 2/13/2007 2:49:05 PM | P | NR |
|
|
would like cover for basememt family room,bathroom and hallway. Phone #: ###-#### met contr, he still had several items to do, said to call for am
|
ELE05-04325
| Final | 2/13/2007 | 2/13/2007 | 2/13/2007 1:57:04 PM | P | PART |
|
|
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia 2nd floor, south part anop ok to final
|
ELE07-00493
| Conference | 2/12/2007 | 2/13/2007 | 2/13/2007 10:26:42 AM | A | DONE |
|
|
marc ###-#### talked about new service and what would be required for grounding and clearances
|
ELE07-00250
| Final | 2/12/2007 | 2/13/2007 | 2/13/2007 9:35:35 AM | A | PASS |
|
|
keith; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, no card to sign
|
ELE07-00323
| Permanent Service | 2/12/2007 | 2/13/2007 | 2/13/2007 9:02:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/12/2007 at 4:54:45 PM. Contact: ###-####. called contr to id gnd conductor, p/s, exst meter pak, n, ok
|
ELE06-00113
| Final | 2/12/2007 | 2/13/2007 | 2/13/2007 8:31:05 AM | A | PASS |
|
|
Contact: Greg Pack Phone #: ###-#### corrections made, did not sign occ card since outstanding correction for elevator, ok to final
|
ELE06-03591
| Final | 2/12/2007 | 2/13/2007 | 2/12/2007 5:27:42 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 2/12/2007 at 5:16:38 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 12 2007 5:27PM.
|