Inspections for the day of: Tuesday, February 13, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00515 INSP-Sprinkler Rough-in/Hydro2/12/20072/13/20072/13/2007 6:44:22 PMPPASS
Underground flush passed.
FIR05-00822 INSP-Sprinkler Rough-in2/13/20072/13/20072/13/2007 6:42:31 PMPPASS
See the city approved plans for the piping locations that are ok to cover
BLD06-01629 FIRE-Final Inspection2/13/20072/13/20072/13/2007 6:40:19 PMPPASS
See the city approved plans for sprinkler piping that is ok to cover.
BLD06-01628 FIRE-Final Inspection2/13/20072/13/20072/13/2007 2:53:09 PMPFAIL
Provide approved door hardware on the main exit and a fire extinguisher as discussed.
FIR06-00651 INSP-Alarm Testing2/13/20072/13/20072/13/2007 2:22:41 PMPPASS
Permit finaled. Items on from last inspection have been corrected.
MIS07-00019 FIR-Final2/9/20072/13/20072/13/2007 12:18:35 PMAPART
A temporary occupancy was given until the sticker at the door is provided, provide fire extinguisher and two sprinkler pendants are too close together and will require a permit to relocate
BLD06-03430 FIRE-Final Inspection2/12/20072/13/20072/13/2007 11:20:45 AMAPASS
life safety passed
FIR06-00917 INSP-Alarm Testing2/12/20072/13/20072/13/2007 10:21:35 AMPFAIL
See Mike Timmerman's inspection report dated today for corrections required.
FIR06-00916 INSP-Alarm Testing2/12/20072/13/20072/13/2007 10:21:15 AMPFAIL
See Mike Timmerman's inspection report dated today for corrections required.
BLD06-02002 FIRE-Final Inspection2/12/20072/13/20072/13/2007 10:20:32 AMAFAIL
Life safety will be ok to pass when the fire alarm permit is finaled
FIR06-00851 INSP-Final Inspection2/12/20072/13/20072/13/2007 10:19:56 AMAFAIL
Horn/strobe in breakroom is mounted above and against a hvac duct. It will need to be relocated away from this obstruction. Test will be called in for tomorrow morning at 8:00am. No devices tested.
BLD06-01566 FIRE-Final Inspection2/12/20072/13/20072/13/2007 10:18:16 AMAPASS
Life safety finaled