Inspections for the day of: Friday, February 13, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00038 INSP-Final Inspection2/13/20092/13/20092/17/2009 8:02:09 AMPPASS
Fire sprinkler permit work finaled.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro2/13/20092/13/20092/17/2009 7:58:41 AMPPART
See approved plans for locations okay for bury.
FIR08-00670 INSP-Final Inspection2/13/20092/13/20092/13/2009 12:59:28 PMPPASS
Fire sprinkler permit finaled.
FIR08-00104 INSP-Alarm Testing2/12/20092/13/20092/13/2009 12:58:40 PMAPART
Walkthrough completed at all floor levels, see plan annotations for areas in need of correction.
FIR08-00815 INSP-Sprinkler Rough-in/Hydro2/12/20092/13/20092/13/2009 12:51:29 PMAPART
Overhead rough-in okayed for cover, be aware of possible obstructions to sprinkler discharge that may develop due to proximity to light fixtures, ceiling fans, structural finishes, etc. when installed. Follow obstruction tables per NFPA 13 for residential head spacing.
BLD08-02566 FIRE-Final Inspection2/12/20092/13/20092/13/2009 12:45:45 PMAFAIL
Need to provide a fire alarm permit for modifications to the existing system as indicated on the approved plan set.
FIR09-00020 INSP-Final Inspection2/12/20092/13/20092/13/2009 12:43:29 PMAPASS
Fire sprinkler permit work passed final inspection.
FIR09-00063 INSP-Final Inspection2/12/20092/13/20092/12/2009 1:58:30 PMAPASS
Scope of fire sprinkler work passed final inspection, one missing retainer strap installed while on site.