BLD13-00032
| FIRE-Final Inspection | 2/13/2013 | 2/13/2013 | 2/13/2013 3:46:15 PM | P | FAIL |
|
|
Currently the mag lock doors are not working. They will need repaired and testes prior to final sign off. All other items appear ok.
|
BLD13-00137
| FIRE-Conference | 2/13/2013 | 2/13/2013 | 2/13/2013 3:36:48 PM | P | DONE |
|
|
Jeremy and I went over smoke alarm placement and general life safety requirements. I deferred his questions on the fire rated assembley to the building inspector.
|
FIR12-00651
| INSP-Sprinkler Rough-in | 2/13/2013 | 2/13/2013 | 2/13/2013 3:29:08 PM | P | PASS |
|
|
Sprinkler piping is ok to cover. Prior to a final sign off contractro needs to provide the original "job site copy" of the plans for review.
|
BLD12-03248
| FIRE-Conference | 2/12/2013 | 2/13/2013 | 2/13/2013 3:24:22 PM | A | DONE |
|
|
Kevin and I went over duct detector placement on the new hvac unit and placement of the fire extinguishers. I also noted that the plans showed 10' racks but actually the racks are 12'. I asked him to discuss with plan review.
|
FIR12-00083
| FIR-Aging Inspection | 2/13/2013 | 2/13/2013 | 2/13/2013 7:43:05 AM | | NR |
|
|
Per steve with simplexgrinnell the DSC permits will be scheduled soon.
|