Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-03353 FIRE-Final Inspection2/13/20142/13/20142/13/2014 4:39:21 PMPPASS
C/N items verified, fire life safety passed.
FIR14-00036 INSP-Final Inspection2/13/20142/13/20142/13/2014 4:35:53 PMPPASS
Verified additional coverage at the new beverage closet. Fire sprinkler permit approved for final.
FIR14-00091 INSP-Final Inspection2/13/20142/13/20142/13/2014 4:29:15 PMPPASS
Corrections verified. Hood suppression permit finaled.
BLD12-01001 FIRE-Final Inspection2/12/20142/13/20142/13/2014 4:14:39 PMPPASS
Fire life safety finaled. C/N items and adjustments finished.
FIR12-00639 INSP-Final Inspection2/12/20142/13/20142/13/2014 4:13:31 PMPPASS
Fire sprinkler permit finaled.
FIR13-00404 INSP-Final Inspection2/12/20142/13/20142/13/2014 4:11:25 PMPPASS
Fire alarm work passed inspection after corrections made while on site.
FIR14-00088 INSP-Final Inspection2/12/20142/13/20142/13/2014 3:07:23 PMPFAIL
C/N items include; notification appliances at some areas need relocated per plan keynote #1, noted overspaced, missing and unsecured notification devices, missing smoke detectors at several areas shown as existing on the plan. Detection and notification spacing has been disrupted due to remodel work and will need revised. Key note items 4 and 5 indicate door holds and a control module which are not provided. Plans do not match field conditions, install does not meet plans.
BLD13-03353 FIRE-Final Inspection2/12/20142/13/20142/13/2014 1:43:25 PMAFAIL
Missing EM lighting at the NW exit passageway, missing exit discharge light at the NW exit, new beverage delivery closet will require fire sprinkler coverage, provide signage at the hood suppression manual pull stations. Project related FIR trade permit finals also pending.
BLD13-03353 FIRE-Alarm Testing2/12/20142/13/20142/13/2014 1:38:14 PMADONE
Duplicate inspection request
FIR14-00091 INSP-Final Inspection2/12/20142/13/20142/13/2014 1:37:15 PMAFAIL
Lights failed to shut down at the west hood, need to provide signage at the manual pull stations indicating hood served, missing necessary documentation including test certification, owner manual, specs and as-built plans.
BLD13-03479 FIRE-Final Inspection2/12/20142/13/20142/13/2014 10:09:38 AMAFAIL
Items noted include; building address, repair one EM light, post fire extinguisher at the first floor office per plan, install field ceiling tile, provide plan modification reflecting change in work scope (west office remodel NA at this time).
FIR13-00404 INSP-Final Inspection2/12/20142/13/20142/13/2014 10:06:01 AMADONE
For inspection completed 2/12 PM- NR due to riser monitoring issues.
FIR14-00052 INSP-Final Inspection2/12/20142/13/20142/13/2014 10:02:26 AMAPASS
Fire sprinkler permit final okay pending field ceiling tile at all areas.
FIR14-00052 INSP-Final Inspection2/12/20142/13/20142/13/2014 10:00:23 AMAPART
Overhead work approved for cover at the remodel areas.