BLD13-03353
| FIRE-Final Inspection | 2/13/2014 | 2/13/2014 | 2/13/2014 4:39:21 PM | P | PASS |
|
|
C/N items verified, fire life safety passed.
|
FIR14-00036
| INSP-Final Inspection | 2/13/2014 | 2/13/2014 | 2/13/2014 4:35:53 PM | P | PASS |
|
|
Verified additional coverage at the new beverage closet. Fire sprinkler permit approved for final.
|
FIR14-00091
| INSP-Final Inspection | 2/13/2014 | 2/13/2014 | 2/13/2014 4:29:15 PM | P | PASS |
|
|
Corrections verified. Hood suppression permit finaled.
|
BLD12-01001
| FIRE-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 4:14:39 PM | P | PASS |
|
|
Fire life safety finaled. C/N items and adjustments finished.
|
FIR12-00639
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 4:13:31 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR13-00404
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 4:11:25 PM | P | PASS |
|
|
Fire alarm work passed inspection after corrections made while on site.
|
FIR14-00088
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 3:07:23 PM | P | FAIL |
|
|
C/N items include; notification appliances at some areas need relocated per plan keynote #1, noted overspaced, missing and unsecured notification devices, missing smoke detectors at several areas shown as existing on the plan. Detection and notification spacing has been disrupted due to remodel work and will need revised. Key note items 4 and 5 indicate door holds and a control module which are not provided. Plans do not match field conditions, install does not meet plans.
|
BLD13-03353
| FIRE-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 1:43:25 PM | A | FAIL |
|
|
Missing EM lighting at the NW exit passageway, missing exit discharge light at the NW exit, new beverage delivery closet will require fire sprinkler coverage, provide signage at the hood suppression manual pull stations. Project related FIR trade permit finals also pending.
|
BLD13-03353
| FIRE-Alarm Testing | 2/12/2014 | 2/13/2014 | 2/13/2014 1:38:14 PM | A | DONE |
|
|
Duplicate inspection request
|
FIR14-00091
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 1:37:15 PM | A | FAIL |
|
|
Lights failed to shut down at the west hood, need to provide signage at the manual pull stations indicating hood served, missing necessary documentation including test certification, owner manual, specs and as-built plans.
|
BLD13-03479
| FIRE-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 10:09:38 AM | A | FAIL |
|
|
Items noted include; building address, repair one EM light, post fire extinguisher at the first floor office per plan, install field ceiling tile, provide plan modification reflecting change in work scope (west office remodel NA at this time).
|
FIR13-00404
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 10:06:01 AM | A | DONE |
|
|
For inspection completed 2/12 PM- NR due to riser monitoring issues.
|
FIR14-00052
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 10:02:26 AM | A | PASS |
|
|
Fire sprinkler permit final okay pending field ceiling tile at all areas.
|
FIR14-00052
| INSP-Final Inspection | 2/12/2014 | 2/13/2014 | 2/13/2014 10:00:23 AM | A | PART |
|
|
Overhead work approved for cover at the remodel areas.
|