ELE15-00397
| Rough-In Permanent Service | 2/12/2015 | 2/13/2015 | 2/13/2015 1:52:54 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman no access to upstairs of garage area. 300.4 Nail plates, framing members with less than 1 1/4 inch clearance to framing member edge require protection called Emmett
|
ELE14-03372
| Final | 2/13/2015 | 2/13/2015 | 2/13/2015 1:11:13 PM | P | FAIL |
|
|
Back door will be open // Mike Phone #: ###-#### 210.8.5 GFI protection required 120 volt receptacles in unfinished basements, unihabitable rooms 334.13 Type NM cable shall be protected from physical damage 210.12 Arc fault protection required in bedroom outlets, new smoke detectors BCC 4.05.26 Trim out inspection, all items required to be functional. GFI at AC, smokes
|
ELE15-00402
| Electrical Rough-In | 2/13/2015 | 2/13/2015 | 2/13/2015 12:23:30 PM | P | PASS |
|
|
Access basement via the egress window well in backyard. Rough in only Call James with any issues Phone #: ###-#### Inspection requested via web by John Harvey Basement RI ok to cover
|
ELE15-00398
| Permanent Service | 2/13/2015 | 2/13/2015 | 2/13/2015 12:06:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk P/S, U/G, N, OK
|
ELE10-02455
| Final | 2/12/2015 | 2/13/2015 | 2/13/2015 11:19:19 AM | A | PASS |
|
|
Ross ###-#### cell Phone #: ###-#### Final OK
|
ELE15-00395
| Electrical Rough-In | 2/12/2015 | 2/13/2015 | 2/13/2015 11:08:26 AM | A | PASS |
|
|
Please call Jim (###-####) 30 minutes ahead for access, best parking is at the back of the building. Phone #: ###-#### Inspection requested via web by Brad Girard discused with contractor, he will fish in replacement wiring to existing rooms, 517.13 all cirucits serving patient care areas be provided with effective ground path, lane 1 and 2, exam room, contact fitting room 517.18 B patient areas shall be provided 8 receptacles. they shall be listed hospital grade. 300.11 cables shall not be supported by grid ceiling, wall cover ok
|
ELE12-02240
| ELE-Aging Inspection | 2/13/2015 | 2/13/2015 | 2/13/2015 10:03:55 AM | | DONE |
|
|
Posted notice on site, 2-13-15, 10am
|
ELE15-00320
| Final | 2/12/2015 | 2/13/2015 | 2/13/2015 9:50:37 AM | A | PASS |
|
|
If you have any questions, please call Calvin. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Final OK
|
ELE15-00320
| Electrical Rough-In | 2/12/2015 | 2/13/2015 | 2/13/2015 9:49:34 AM | A | PASS |
|
|
If you have any questions, please call Calvin. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan RI OK
|
ELE13-00057
| Final | 2/13/2015 | 2/13/2015 | 2/13/2015 8:50:28 AM | P | PASS |
|
|
Existing sign that was installed in 1981, this permit replaced the placard fronts of the sign. Final OK
|
ELE13-00057
| ELE-Aging Inspection | 2/13/2015 | 2/13/2015 | 2/13/2015 8:50:20 AM | | DONE |
|
|
|