Inspections for the day of: Friday, February 13, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00397 Rough-In Permanent Service2/12/20152/13/20152/13/2015 1:52:54 PMPFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman
no access to upstairs of garage area.
300.4 Nail plates, framing members with less than 1 1/4 inch clearance to framing member edge require protection
called Emmett
ELE14-03372 Final2/13/20152/13/20152/13/2015 1:11:13 PMPFAIL
Back door will be open // Mike Phone #: ###-####
210.8.5 GFI protection required 120 volt receptacles in unfinished basements, unihabitable rooms
334.13 Type NM cable shall be protected from physical damage
210.12 Arc fault protection required in bedroom outlets, new smoke detectors
BCC 4.05.26 Trim out inspection, all items required to be functional. GFI at AC, smokes
ELE15-00402 Electrical Rough-In2/13/20152/13/20152/13/2015 12:23:30 PMPPASS
Access basement via the egress window well in backyard. Rough in only
Call James with any issues Phone #: ###-#### Inspection requested via web by John Harvey
Basement RI ok to cover
ELE15-00398 Permanent Service2/13/20152/13/20152/13/2015 12:06:47 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
P/S, U/G, N, OK
ELE10-02455 Final2/12/20152/13/20152/13/2015 11:19:19 AMAPASS
Ross ###-#### cell Phone #: ###-####
Final OK
ELE15-00395 Electrical Rough-In2/12/20152/13/20152/13/2015 11:08:26 AMAPASS
Please call Jim (###-####) 30 minutes ahead for access, best parking is at the back of the building. Phone #: ###-#### Inspection requested via web by Brad Girard
discused with contractor, he will fish in replacement wiring to existing rooms, 517.13 all cirucits serving patient care areas be provided with effective ground path, lane 1 and 2, exam room, contact fitting room
517.18 B patient areas shall be provided 8 receptacles. they shall be listed hospital grade.
300.11 cables shall not be supported by grid ceiling,
wall cover ok
ELE12-02240 ELE-Aging Inspection2/13/20152/13/20152/13/2015 10:03:55 AM DONE
Posted notice on site, 2-13-15, 10am
ELE15-00320 Final2/12/20152/13/20152/13/2015 9:50:37 AMAPASS
If you have any questions, please call Calvin. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
Final OK
ELE15-00320 Electrical Rough-In2/12/20152/13/20152/13/2015 9:49:34 AMAPASS
If you have any questions, please call Calvin. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
RI OK
ELE13-00057 Final2/13/20152/13/20152/13/2015 8:50:28 AMPPASS
Existing sign that was installed in 1981, this permit replaced the placard fronts of the sign. Final OK
ELE13-00057 ELE-Aging Inspection2/13/20152/13/20152/13/2015 8:50:20 AM DONE