Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00870 INSP-Final Inspection2/5/20152/10/2015 P 
Forrest, The school district would like to schedule the test for 3:30 on Tuesday if at all possible. Please let me know as soon as possible if that will work so I can confirm it with them. Thank you. Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick
FIR14-00708 INSP-Sprinkler Rough-in2/10/20152/10/2015 P 
Rough to cover 2nd floor F. ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Carter II
FIR14-00681 INSP-Sprinkler Rough-in/Hydro2/10/20152/10/2015 P 
Partial rough to cover bldg D 1st floor (soffits/hard lids ) ###-#### Leroy >> Inspection requested via web by Scott Carter II
FIR15-00080 INSP-Sprinkler Rough-in2/13/20152/13/20152/13/2015 4:26:43 PMPCANC
Jeff Phone #: ###-#### *Mistaken permit number request*
FIR14-00068 INSP-Supply line flush2/13/20152/13/20152/13/2015 4:13:34 PMPPART
UG fire supply line flush completed
FIR14-00069 INSP-Supply line flush2/13/20152/13/20152/13/2015 4:13:29 PMPPART
UG fire supply line flush completed
FIR14-00531 INSP-Conference2/12/20152/13/20152/13/2015 2:57:16 PMADONE
On site conferecne regarding NFPA 13 2013 sec. 8.5.5.4
FIR14-00478 INSP-Sprinkler Rough-in2/12/20152/13/20152/13/2015 2:55:28 PMAPART
UG fire supply line flush completed satisfactory.
FIR14-00815 INSP-Sprinkler Rough-in2/12/20152/13/20152/13/2015 1:42:17 PMAPART
Rough-in at the 2nd floor section one living units south-side of the north corridor completed. Missing hanger at bedroom unit 229, overspaced sprinkler coverage at unit 234. Discussed coverage at concealed pipe chases per plan. Verified previous correction items at the north side units.
BLD14-02759 FIRE-Final Inspection2/12/20152/13/20152/13/2015 11:57:32 AMANR
Need project related fire alarm and fire sprinkler permit work requested for final inspections prior to fire life safety approval.
FIR15-00100 INSP-Final Inspection2/12/20152/13/20152/13/2015 9:04:47 AMAPASS
Fire alarm permit finaled.
FIR14-00792 INSP-Supply line flush2/13/20152/13/20152/13/2015 8:07:51 AMPCANC
Please call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt