Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00569 Final2/13/20182/13/20182/13/2018 2:55:29 PMPFAIL
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
300.15- All wiring shall terminate in a box. Roof old sign removed. Open wiring.
330.30(B)- MC shall be secured with in 12" of a box. UC receptacles.
356.30- Non-metallic seal tight on east condensing unit new, shall be secured with in 12" of terminations.
404.8- Circuit directories shall be updated. Ensure all unused circuits have been disconnected.
314.17(A)- All unused openings shall be closed. West condensing units removed.
* Note from Fire Marshal on site states furnace shall be relocated with clearences as per manufacturers spec.
BCC 4-05-32 Code violations not to be retained. As leaving noticed receptacle recessed in wall with out proper cover. Caulking around perimeter of receptacle.
ELE17-04230 Final2/13/20182/13/20182/13/2018 1:51:13 PMPPASS
Please call for code to get in Phone #: ###-#### Inspection requested via web by Robert Murray Final ok
ELE17-04092 Final2/13/20182/13/20182/13/2018 1:10:13 PMPPASS
Robert Phone #: ###-####
Final ok
ELE17-04092 Electrical Rough-In2/13/20182/13/20182/13/2018 12:40:58 PMPPASS
Robert Phone #: ###-####
Heat pump addition rough in ok
ELE18-00550 Electrical Rough-In2/12/20182/13/20182/13/2018 11:13:00 AMAPASS
Roger Bachman is the contact onsite Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Wall rough in ok cover
ELE18-00163 Final2/12/20182/13/20182/13/2018 10:29:50 AMAFAIL
Final Inspection for Cell Site Tower
Contact Steve Hess
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
110.24- Available fault current shall be posted with the date calculated on all services.
ELE17-03842 Final2/12/20182/13/20182/13/2018 9:39:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Christy Cheney
Signed shell card in job office trailer.
Final ok