Inspections for the day of: Tuesday, February 13, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00187 FIR-Aging Inspection2/13/20182/13/20182/16/2018 11:13:41 AM NR
I've spoken to Bill Harmon and Ray with the boise school district and people at Simplex about getting this permit finaled
FIR16-00628 INSP-Final Inspection2/12/20182/13/20182/13/2018 2:51:17 PMPPART
I verified head end equipment and smoke detectors for door release in the corridors. One pair of doors did not latch. There are delayed egress doors installed that will need to be connected to the fire alrm system for releaseas per the IFC. The accordian fire doors have not been installed yet. Still need to test devices in the individual rooms. The sounder bases in the individual rooms need to sound upon genereal alarm (see alarm matrix). Need to test the fire sprinkler devices and the duct detectors for hvac unit shutdown. Signals have been verified for the devices tested today.

Contact is Dirk Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD17-03778 FIRE-Final Inspection2/13/20182/13/20182/13/2018 2:28:38 PMPFAIL
Provide city approved plans and notes, provide installation that matches the approved plans such as fire extinguisher layout and exit signs and emergency lights and exit discharge lights. Exit discharge lights can not be on timer or photo sensor.

CODY JONES Phone #: ###-####
BLD18-00464 FIRE-Final Inspection2/12/20182/13/20182/13/2018 2:22:12 PMPFAIL
Repair exit signs/emergency lights. Provide testing of lights, provide exit discharge light at the east exit door, provide single action hardware for the restroom door and office/storage room door.

Steve Phone #: ###-####
FIR18-00105 INSP-Final Inspection2/13/20182/13/20182/13/2018 11:40:11 AMPPASS
Permit finaled

Adam Phone #: ###-####
BLD17-03534 FIRE-Final Inspection2/13/20182/13/20182/13/2018 11:18:22 AMPPASS
Life safety passed

Any time Phone #: ###-#### Inspection requested via web by Don Steinke
FIR17-00705 INSP-Final Inspection2/12/20182/13/20182/13/2018 11:06:45 AMAPASS
Permit finaled. Hood suppression system functioned.

Phone #: ###-####
NAF18-00003 INSP-Final2/12/20182/13/20182/13/2018 11:06:15 AMAFAIL
Provide plans, provide Suite number, provide sticker at the main exit as discussed

Call for access Phone #: 2084842354 >> Inspection requested via mobile web by Mr. Nahass
NAF18-00008 INSP-Final2/12/20182/13/20182/13/2018 9:03:06 AMAFAIL
Provide annuall inspection for the fire extinguisher, remove the thumbturn deadbolt and provide keyed with sticker as discussed, provide singel action hardware as discussed at the main exit.


Call for access Phone #: 2088701596 >> Inspection requested via mobile web by Nana Hancock
BLD17-02654 FIRE-Final Inspection2/12/20182/13/20182/13/2018 8:40:37 AMAFAIL
Provide two additional fire extinguishers as discussed and relocated the new smoke alarms to atleast 3'-0" from the air diffusers and restroom doors.

Steve Phone #: ###-####