Inspections for the day of: Wednesday, February 13, 2019.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05387 Final2/13/20192/13/20192/13/2019 3:53:19 PMPPASS
MEC AND FIREPL Phone #: ###-#### Inspection requested via web by Oleg Chervak
- final ok
MEC19-00651 Final2/13/20192/13/20192/13/2019 3:22:09 PMPPASS
Please contact Brian Eddin''s with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Joshua Bennett
- final ok on three offices supply and return ok
MEC19-00600 Final2/12/20192/13/20192/13/2019 3:04:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-00631 Pressure Test2/13/20192/13/20192/13/2019 2:38:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 20lb gas pressure test for furnace ok
MEC18-04702 Rough-in2/13/20192/13/20192/13/2019 2:05:39 PMPPASS
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- area B caffateria and theater and corridor soffits with duct work ok for cover duct seal ok
MEC19-00463 Final2/12/20192/13/20192/13/2019 1:23:54 PMPCANC
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- should have been a pressure test
- final will be later when equipment is installed
MEC19-00463 Pressure Test2/13/20192/13/20192/13/2019 1:23:20 PMPPASS
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- 20lb gas pressure test ok
- tagged meter bar
- check for insulation sheild on flue at final
MEC19-00583 Pressure Test2/12/20192/13/20192/13/2019 1:11:58 PMPCANC
Phone #: ###-#### Inspection requested via web by Gary Reeves
MEC19-00583 Rough-in2/12/20192/13/20192/13/2019 1:11:33 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
- need man J stamped and onsite
MEC19-00631 Pressure Test2/12/20192/13/20192/13/2019 11:05:32 AMAFAIL
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- 20lb pressure test was under 20lb needs to be tested on a 30lb gauge at least 20lb for 20mins
- sectional test needs to have a double valve open ended tee installed at live gas line or be disconnected from live gas for test
- reschedule pressure test for afternoon
MEC19-00622 Final2/12/20192/13/20192/13/2019 10:46:43 AMAPASS
Call ahead to Randy at ###-#### when in route. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
- furnace only co ok
MEC19-00498 Final2/12/20192/13/20192/13/2019 10:35:46 AMAPASS
Inspection requested via web by Margie Rowe
- furnace ac coil co ok
MEC19-00635 Pressure Test2/12/20192/13/20192/13/2019 10:19:18 AMAFAIL
PLEASE CALL CONTRACTOR NATE WHEN EN ROUTE FOR PRESSURE TEST ON NEW GAS LINE. Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
- gauge under 20lb
- need to add supports to gas line in crawl
- need to see range hood vent added to permit
MEC19-00642 Rough-in2/12/20192/13/20192/13/2019 10:05:27 AMAPASS
Rough in inspection for basement remodel, Bathroom exhaust fan, new returns and supply. Please call with any questions. Thank you. Phone #: ###-#### Inspection requested via web by Gary Duncan
- R/I ok
- Cover ok
MEC18-01953 Mec-Aging Inspection2/13/20192/13/20192/13/2019 8:10:49 AM DONE
talked with TML about checking the status of the permit. If ready schedule inspection with homeowner