Inspections for the day of: Thursday, February 13, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00617 Final2/12/20202/13/20202/13/2020 2:17:14 PMPNR
Please inspect PM and call Dave on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- still installing- reschedule when complete
MEC20-00535 Pressure Test2/6/20202/13/20202/13/2020 2:16:48 PMPFAIL
PLEASE CALL WHEN ON THE WAY. THANK YOU Phone #: ###-#### Inspection requested via web by SARA GREENHALGH- gauuge under 20psi
MEC20-00098 Rough-in2/12/20202/13/20202/13/2020 1:10:19 PMPPART
Rough In inspection Building #12. @ 2 pm if possible. Please call Shawn at ###-#### with any questions Phone #: ###-#### Inspection requested via web by Amanda Casper- units K 101 102 103 104 201202 203 and 204 seal on duct ok- ok to cover- units K105 106 205 206 305 and 306 still need engineer to submit drawings to city for review on fire dampers that were missed and have approved drawings onsite to grant cover on these units- GC was not onsite to talk to- call in R/I when fire dampers have been addressed and approved thru city and onsite
MEC20-00557 Rough-in2/12/20202/13/20202/13/2020 11:06:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC20-00557 Pressure Test2/12/20202/13/20202/13/2020 11:02:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location- 5lb flue pass
MEC19-04742 Final2/12/20202/13/20202/13/2020 10:18:53 AMAFAIL
Special instructions for access...please call 5 - 10 minutes before you arrive.
thank you.... Phone #: ###-#### Inspection requested via web by Bruce Lacy
1- need to seal exterior lineset penetration
2- need 90 degree pvc on condesate drain outside and seal weather tight thru foundation
3- need to seal gas piping thru wall at meter
4- need 6" clearance from flue to pvc drain in closet
5- need to add pipe to dryer duct in laundry room
6- seal condensate at floor in furnace closet where penetrates into crawl
MEC20-00519 Final2/12/20202/13/20202/13/2020 9:29:26 AMAPASS
Please call MJ on your way ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
MIS20-00041 MEC-Conference2/7/20202/13/20202/13/2020 8:45:06 AMAPEND
check on permit issued for mech work- talked with Jose said home needed acca report- they will pull permit once bld permit issued and acca report complete
MEC20-00562 Final2/10/20202/13/20202/13/2020 8:42:12 AMAPASS
Adrienne is available from 8-12pm and would like a 30 minute pre-call prior to arrival if possible. Phone #: ###-#### Inspection requested via web by Andrea Grigsby- furnace a/c coil co locking caps ok
MEC19-01771 Mec-Aging Inspection2/13/20202/13/20202/13/2020 8:08:17 AM CANC
permit expired
MEC19-01771 DOC - Permit Expired2/13/20202/13/20202/13/2020 8:08:00 AMAPASS
no calls- no activity- permit expired