Inspections for the day of: Wednesday, February 14, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00516 Electrical Rough-In2/14/20072/14/20072/14/2007 4:09:27 PMPPASS
Inspect walls for cover only. Please call if you have any questions. Thanks Jeff Phone #: ###-#### walls only downstairs ok to cover
ELE07-00524 Electrical Rough-In2/14/20072/14/20072/14/2007 2:59:30 PMPPASS
trench inspection Phone #: ###-#### ok to cover trench
ELE06-04055 Electrical Rough-In2/14/20072/14/20072/14/2007 2:03:02 PMPFAIL
jerrod; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left message, nec 680.10 and 300.5 u/g cnd shall be min 18" deep
ELE06-04457 Final2/13/20072/14/20072/14/2007 1:28:43 PMPPART
bob - partial occupancy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith signed struct card for part t/o, left corr notice,nec 408.4 panel schedule shall be complete, clear and concise, 300.11(A)(1) no low voltage wiring shall be on ceiling, 725.3(B) abandoned lv cable shall be removed, talked to contractor
ELE06-03591 Final2/12/20072/14/20072/14/2007 11:42:58 AMAPASS
Scheduled by a contractor via Hello! on 2/12/2007 at 5:22:15 PM. Contact: ###-####. ok to final
ELE06-04191 Permanent Service2/13/20072/14/20072/14/2007 10:18:09 AMAFAIL
fred ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr., left corr notice, nec 250.24(A) grounding electrode conductor shall be connected to grounded service conductor
ELE07-00507 Final2/13/20072/14/20072/14/2007 9:43:46 AMAPASS
Call ###-#### before you arrive to gain access. Work performed by Nick Felsted. Phone #: ###-#### ri and final ok
ELE07-00506 Electrical Rough-In2/13/20072/14/20072/14/2007 8:47:14 AMAPASS
Ready for final. Jason(tech). Store opens 8:00am, the earlier the better. Manager is Anna Phone #: ###-#### ri ok see final
ELE07-00506 Final2/14/20072/14/20072/14/2007 8:46:42 AMAPASS
Ready for final. Jason(tech). Store opens 8:00am, the earlier the better. Manager is Anna Phone #: ###-#### ok to final
ELE07-00026 Electrical Rough-In2/13/20072/14/20072/14/2007 8:21:40 AMAPASS
Phone #: ###-#### walls east 1/2 only ok to cover, told elect to put on nail plates
ELE06-04592 Electrical Rough-In2/13/20072/14/20072/14/2007 7:52:47 AMAPART
lea - borders - 1047 ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith soffit ok to cover anop