Inspections for the day of: Wednesday, February 14, 2007.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00849 FIRE-Final Inspection2/14/20072/14/20072/15/2007 5:58:41 AMPCANC
There was no time for inspection. Will need to reschedule.
BLD04-00941 FIRE-Sprinkler Rough-in2/14/20072/14/20072/15/2007 5:57:03 AMPCANC
There was no time for inspection. Will need to reschedule
FIR06-00518 INSP-Sprinkler Rough-in/Hydro2/14/20072/14/20072/14/2007 3:49:58 PMPPASS
underground hydro test passed
FIR07-00085 INSP-Alarm Testing2/13/20072/14/20072/14/2007 3:47:45 PMPCANC
Contractor was not ready the first time I showed up at the project. It was later decided to reschedule for when the elevator people could be there.
BLD05-01077 FIRE-Final Inspection2/14/20072/14/20072/14/2007 3:22:56 PMPFAIL
All items on the correction notice have been taken care of. I signed the sign-off card. But befor I could make a computer entry I was contacted by Sam ROges about a sprinkler issue above the lobby ceiling. I told Dennis that there would be no sign off from me until the issue is resolved. He is going to take care of the issue and then contact me.
BLD06-01260 FIRE-Final Inspection2/13/20072/14/20072/14/2007 3:08:03 PMAPASS
Life safety finaled
FIR05-00425 INSP-Final Inspection2/13/20072/14/20072/14/2007 2:49:52 PMAPASS
permit finaled. The last item on Dennis's correction notice, which was the head box has been corrected.
FIR07-00098 INSP-Final Inspection2/14/20072/14/20072/14/2007 2:10:28 PMPFAIL
Contractor did not have smoke to test the detector and there was no water in the fire sprinkler system to test the flow switch. The tamper switches did operate however.
FIR06-00990 INSP-Final Inspection2/14/20072/14/20072/14/2007 1:09:39 PMPCANC
Project was not ready for an inspection.
BLD04-03025 FIRE-Final Inspection2/14/20072/14/20072/14/2007 12:10:56 PMPPASS
Life safety finaled
FIR05-00509 INSP-Final Inspection2/13/20072/14/20072/14/2007 11:45:01 AMAPASS
Permit finaled Troy ###-####
BLD06-03162 FIRE-Final Inspection2/12/20072/14/20072/14/2007 11:40:43 AMAFAIL
Life safety was not ready and the fire alarm a/v in the corridor was mounted too low. No inspections performed.
MIS07-00024 FIR-Final2/12/20072/14/20072/14/2007 11:39:15 AMAFAIL
Provide annual inspection for the fire extinguishers, mount fire extinguisher in space 116, infill the door as per plans on the east side of space 116, cover open electrical boxes in elevator pit, provide 4" address numbers, remove thumbturn from the west/main exit of space 116 and provide sticker if keyed hardware is utilized, cover insulation in space 116 as per the product listing, provide single function actuation for hardware in the ada compliant restroom.
MIS07-00023 FIR-Final2/12/20072/14/20072/14/2007 11:35:27 AMAFAIL
Provide updated annual inspection for the fire extinguishers.
BLD06-02830 FIRE-Final Inspection2/14/20072/14/20072/14/2007 9:49:42 AMPPASS
Life safety passed.
FIR07-00112 INSP-Final Inspection2/13/20072/14/20072/14/2007 9:28:52 AMAPASS
permit finaled
FIR07-00058 INSP-Final Inspection2/13/20072/14/20072/14/2007 9:28:26 AMPPASS
Hood suppression system operated correctly
BLD06-02002 FIRE-Final Inspection2/13/20072/14/20072/14/2007 8:52:41 AMAPASS
Life safety passed. I noticed that the second floor fire door infront of the second floor elevator hung up on the carpet. The building maintenance official stated that he would contact his officee to get the work started
FIR06-00851 INSP-Final Inspection2/13/20072/14/20072/14/2007 8:44:54 AMAPASS
Permit finaled. An updated map with walls will be required to be provided to the owner.
BLD06-02887 FIRE-Final Inspection2/13/20072/14/20072/14/2007 12:00:00 AMACANC
rob; Phone #: ###-#### Internet Inspection Request from: Victoria Beall