Inspections for the day of: Thursday, February 14, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01485 Final2/14/20082/14/20082/14/2008 4:13:29 PMPPASS
ok to final
ELE06-02960 Final2/12/20082/14/20082/14/2008 3:42:35 PMPCANC
SCOTT Phone #: ###-#### Internet Inspection Request from: Sean DeLacy went to site, called contractor, he wanted to schedule for am
ELE07-02451 Electrical Rough-In2/14/20082/14/20082/14/2008 3:01:27 PMPCANC
R.I. cover inspection. Please call Rick Sendra prior to inspection. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson see conference
ELE07-02451 Conference2/14/20082/14/20082/14/2008 3:01:14 PMPDONE
R.I. cover inspection. Please call Rick Sendra prior to inspection. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson talked about panel clearances, borders for ceilings, cable tray over panels- no borders shall be installed before room inspection
ELE08-00365 Temporary Service2/14/20082/14/20082/14/2008 1:54:50 PMPFAIL
jim Phone #: ###-#### called, left correction notice, BCC job id sticker shall be posted, NEC 312.5 all conductors entering enclosure shall have abrasion protection, fee due
ELE08-00349 Rough-In Permanent Service2/14/20082/14/20082/14/2008 1:15:25 PMPCANC
Sorry for the am/pm confusion. Happy Valentine Day!! Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see ri and p/s
ELE08-00349 Permanent Service2/14/20082/14/20082/14/2008 1:15:06 PMPFAIL
Sorry for the am/pm confusion. Happy Valentine Day!! Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson told electrician, left correction notice, NEC 110.26(F)(2)) depth of working space shall be provided at service- no other equipment shall be located in this zone
ELE08-00349 Electrical Rough-In2/14/20082/14/20082/14/2008 12:57:42 PMPPASS
Sorry for the am/pm confusion. Happy Valentine Day!! Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok
ELE08-00347 Rough-In Permanent Service2/13/20082/14/20082/14/2008 10:34:36 AMACANC
Circuit ran for new hot tub, ready for your final approval. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST see ri, wrong type request
ELE08-00347 Electrical Rough-In2/14/20082/14/20082/14/2008 10:18:28 AMANR
Circuit ran for new hot tub, ready for your final approval. Phone #: ###-#### Internet Inspection Request from: BRENDA HURST still working on job for u/g and receptacle, no hot tub on site, fee due
ELE08-00342 Conference2/12/20082/14/20082/14/2008 10:00:03 AMADONE
bruce Phone #: ###-#### talked about classification of area per prints and contractor building and labelling and listing control panel for area
ELE08-00257 Electrical Rough-In2/13/20082/14/20082/14/2008 9:02:05 AMAPASS
calvin Phone #: ###-#### ok to backfill concrete encased electrode
ELE08-00257 Permanent Service2/14/20082/14/20082/14/2008 8:58:56 AMAPASS
calvin Phone #: ###-#### p/s o/h n ok
ELE08-00226 Permanent Service2/13/20082/14/20082/14/2008 8:47:59 AMAPASS
mike Phone #: ###-#### p/s, exst meter pak, n, ok
ELE08-00217 Final2/13/20082/14/20082/14/2008 8:08:08 AMAPASS
This is a final inspection please. Contact Loe Lopez Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok to final, signed occupancy card