Inspections for the day of: Tuesday, February 14, 2012.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00563 INSP-Sprinkler Rough-in/Hydro2/14/20122/14/20122/14/2012 3:31:44 PMPCANC
Canceled and rescheduled for tomorrow per Raul voice message.
BLD10-02069 FIRE-Conference2/14/20122/14/20122/14/2012 3:03:58 PMPDONE
Carl Westfall and I performed a job site review of the exit signs in areas A and B. I let the superintendant Scott know that they need to be installed as per approved plans and the two that are blocked by the low soffits will need to be viewable from the far end of the corridor.
FIR12-00052 INSP-Final Inspection2/14/20122/14/20122/14/2012 2:55:18 PMPPASS
Permit finaled. Randy needs to provide as-builts showing the correct location of the duct smoke detectors
FIR11-00612 INSP-Final Inspection2/13/20122/14/20122/14/2012 2:30:52 PMPPASS
Permit finaled. Tamper switches tested to the facp.
FIR11-00642 INSP-Final Inspection2/13/20122/14/20122/14/2012 11:22:28 AMAFAIL
The corrections I had red lined have been addressed and the duct smoke detectors tested. As-builts will be needed showing the correct hvac unit/detector. Need the NAC circuits tested, sprinkler flow switches tested, a print out of the signals tested and final paper work for a final sign off.
FIR11-00479 INSP-Sprinkler Rough-in2/13/20122/14/20122/14/2012 9:29:50 AMAPASS
The sprinkler piping in Corridor 222 can be covered. As-builts are approved. To final the project a sticker is needed for the outside alarm bell, forward flush of the backflow, sprinkler work finished at the main entry/foirer and testing of the flow switches. Also a sprinkler system coverage/zone map is needed at the risers for fire dept use.
BLD11-02578 FIRE-Final Inspection2/13/20122/14/20122/14/2012 7:35:36 AMAPASS
Life safety passed. The security grill is being cut down and the welded leaf of the north exit door is being blocked off with a wall extention.