Inspections for the day of: Wednesday, February 14, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00775 INSP-Sprinkler Rough-in2/14/20182/14/20182/14/2018 3:17:28 PMPPASS
The sprinkler piping in the scope of work can be covered. As-builts need to be provided showing all work such as the change out of pendant heads to quick responce.

Please call Jeff With time frame Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD17-04514 FIRE-Final Inspection2/13/20182/14/20182/14/2018 3:07:34 PMPFAIL
Provide city approved plans and small docments, cover arrow on the exit sing near the main exit, provide a fire extinguisher near the south end of the building. Possibly speak with plans review about the door that has been disabled.

Phone #: ###-#### Inspection requested via web by Scott Simons
FIR18-00025 INSP-Sprinkler Rough-in2/14/20182/14/20182/14/2018 2:01:06 PMPPASS
Hard lid inspection in shower room passed. Piping can be covered.
BLD17-03778 FIRE-Final Inspection2/13/20182/14/20182/14/2018 2:00:31 PMAPART
A temporary for life safety is being given with Scott's approval until the exit discharge light is installed at the main exit and sprinkler protection is provided under the new stairs to the mezzanine.

Cody Phone #: ###-####
FIR17-00412 INSP-Sprinkler Rough-in2/14/20182/14/20182/14/2018 10:50:59 AMPPART
Rough-in for the overhead piping passed. Still missing acouple of earthquake braces that will be checked later. will need another cover inspection when the pendant drops have been installed. Per the contractor the architectural features in the main hallway will not have ceilings installed so it will allow the water from the upright sprinklers to provide protection.


Mike Martin is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-00464 FIRE-Final Inspection2/14/20182/14/20182/14/2018 10:47:14 AMPPASS
Life safety passed

Steve Phone #: ###-####
BLD17-02654 FIRE-Final Inspection2/13/20182/14/20182/14/2018 9:10:04 AMAPASS
Life safety passed.


Steven Phone #: ###-####
FIR17-00489 INSP-Supply line flush2/13/20182/14/20182/13/2018 3:13:55 PMPCANC
1 pm if that works for you Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
FIR17-00493 INSP-Supply line flush2/13/20182/14/20182/13/2018 3:13:21 PMPCANC
1 pm if that works for you. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball