ELE19-00558
| Electrical Rough-In | 2/14/2019 | 2/14/2019 | 2/14/2019 2:56:26 PM | P | PASS |
|
|
Please call when on your way.
Need inspection for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean From base of pole to in ground box 3' to 4' from in length rough in ok cover
|
ELE18-02369
| Electrical Rough-In | 2/12/2019 | 2/14/2019 | 2/14/2019 2:02:26 PM | P | PASS |
|
|
Call Joey C prior to arrival. Rough in for hardlids floors 2-4. Phone #: ###-#### Inspection requested via web by Scott Campbell Levels 2,3,4 elevator lobbies and tape lighting wiring and level 5 tape wiring only as noted on contractor print rough in ok cover
|
ELE18-04448
| Permanent Service | 2/13/2019 | 2/14/2019 | 2/14/2019 12:32:31 PM | A | PASS |
|
|
Please contact Tim Arnold before arrival. Thank you. Phone #: ###-#### Inspection requested via web by Kerri Hamilton p/s u/g n ok
|
ELE19-00205
| Conference | 2/13/2019 | 2/14/2019 | 2/14/2019 11:45:00 AM | A | PASS |
|
|
call for access- Lee Phone #: ###-#### Owner to install minimum required for shop, 1 auto bay, 1 man door, 1 luminaire, discussed protections of NM cables below 8', tamper resistant receptacles, GFCI protection, pamphlet given.
|
ELE19-00468
| Permanent Service | 2/13/2019 | 2/14/2019 | 2/14/2019 10:53:41 AM | A | FAIL |
|
|
Ufer ground and Permanent Service please Phone #: ###-#### Inspection requested via web by Winters LLC 250.52(A)(3)- Grounding electrode system not complete, rebar present but not encased in concrete yet. Recall permenant service when concrete encased pour complete.
|
ELE19-00468
| Electrical Rough-In | 2/14/2019 | 2/14/2019 | 2/14/2019 10:30:53 AM | P | PASS |
|
|
Ufer ground and Permanent Service please Phone #: ###-#### Inspection requested via web by Winters LLC Concrete encased electrode rough in ok cover
|
ELE19-00573
| Electrical Rough-In | 2/13/2019 | 2/14/2019 | 2/14/2019 10:20:38 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Angela Stears 210.70(A)(2)(2)- At least one wall swtch controlled lighting outlet shall be installed to provide illumination on exterior side of outdoor entrances. Mandoor. 225.31- A means shall be provided to disconnect all ungrounded conductors from detached garage.
|
ELE18-04856
| Final | 2/13/2019 | 2/14/2019 | 2/14/2019 9:43:03 AM | A | PASS |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|