Inspections for the day of: Thursday, February 14, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00558 Electrical Rough-In2/14/20192/14/20192/14/2019 2:56:26 PMPPASS
Please call when on your way.

Need inspection for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean
From base of pole to in ground box 3' to 4' from in length rough in ok cover
ELE18-02369 Electrical Rough-In2/12/20192/14/20192/14/2019 2:02:26 PMPPASS
Call Joey C prior to arrival. Rough in for hardlids floors 2-4. Phone #: ###-#### Inspection requested via web by Scott Campbell
Levels 2,3,4 elevator lobbies and tape lighting wiring and level 5 tape wiring only as noted on contractor print rough in ok cover
ELE18-04448 Permanent Service2/13/20192/14/20192/14/2019 12:32:31 PMAPASS
Please contact Tim Arnold before arrival. Thank you.
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
p/s u/g n ok
ELE19-00205 Conference2/13/20192/14/20192/14/2019 11:45:00 AMAPASS
call for access- Lee Phone #: ###-####
Owner to install minimum required for shop, 1 auto bay, 1 man door, 1 luminaire, discussed protections of NM cables below 8', tamper resistant receptacles, GFCI protection, pamphlet given.
ELE19-00468 Permanent Service2/13/20192/14/20192/14/2019 10:53:41 AMAFAIL
Ufer ground and Permanent Service please Phone #: ###-#### Inspection requested via web by Winters LLC
250.52(A)(3)- Grounding electrode system not complete, rebar present but not encased in concrete yet. Recall permenant service when concrete encased pour complete.
ELE19-00468 Electrical Rough-In2/14/20192/14/20192/14/2019 10:30:53 AMPPASS
Ufer ground and Permanent Service please Phone #: ###-#### Inspection requested via web by Winters LLC
Concrete encased electrode rough in ok cover
ELE19-00573 Electrical Rough-In2/13/20192/14/20192/14/2019 10:20:38 AMAFAIL
Phone #: ###-#### Inspection requested via web by Angela Stears
210.70(A)(2)(2)- At least one wall swtch controlled lighting outlet shall be installed to provide illumination on exterior side of outdoor entrances. Mandoor.
225.31- A means shall be provided to disconnect all ungrounded conductors from detached garage.
ELE18-04856 Final2/13/20192/14/20192/14/2019 9:43:03 AMAPASS
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok